MODEL
/TYPE
AMPERE
SIZE SWITCHED
POLES
ENCLOSURE TYPE
OPERATIONAL VOLTAGE
ACCESSORIES
A B
Consult Table Below
Type 1 Enclosure
Open Style Unit
B
2 Poles
F
4 Poles
E
3 Poles
B 0
Z
B
0
Z E C
Z V C
T D
S
M
CONTROL
PANEL
Switch Types
•
Standard:
Unless otherwise noted, the
standard switch with quick transfer will
be supplied.
•
Delayed Transition:
When ordered as
the ZTSD, the delayed transition switch
offers time delay during transfer from one
position to the other. This is primarily for
transfer of large motor or inductive loads.
•
Closed Transition:
When ordered as the
ZTSCT
, the closed transition switch offers
two basic modes of operation. During
a failure of one source or an out of specifi-
cation condition, the ZTSCT Model oper-
ates as a standard delayed transition
switch (ZTSD Model). This sequence allows
clear separation of an unreliable source
from an available one.
•
Bypass:
When ordered as the ZBTS, the
bypass transition switch offers a draw-out
mechanism, with electrical and mechanical
interlocks for secure removal after load
bypass. In this way the transfer switch
and/or the control panel may be tested,
isolated and removed for maintenance
without load interruption.
Then choose
additional accessories
APPLICATION
0
Utility - Generator
M
Manual
G
Gen to Gen
U
Utility - Utility
Type 4 Enclosure
Type 12 Enclosure
Type 4X Enclosure
Type 3R Enclosure
0 1
1 2
3 R
4 0
4 X
0 0
A
B
Voltage Phase
Con
fi
g. Hz
1
0
120
1
2 wire
60
2
0
120/240
1
3 wire
60
2
2
110/220
1
3 wire
50
3
0
240
3
3 wire
60
3
1
208
3
3 wire
60
3
2
220
3
3 wire
50
3
5
139/240
3
4 wire
60
4
0
120/208
3
4 wire
60
4
1
127/220
3
4 wire
60
4
2
127/220
3
4 wire
50
5
0
480
3
3 wire
60
5
1
440
3
3 wire
60
5
2
440
3
3 wire
50
5
5
460
1
3 wire
50
5
7
480
1
2 wire
60
5
8
254/440
3
4 wire
60
6
0
575
3
3 wire
60
6
1
347/600
3
4 wire
60
6
3
575
1
2 wire
60
7
0
277/480
3
4 wire
60
7
1
277
1
2 wire
60
7
4
266/460
3
4 wire
60
7
5
460
3
3 wire
60
8
2
380
1
2 wire
50
9
0
240/416
3
4 wire
60
9
1
220/380
3
4 wire
60
9
2
220/380
3
4 wire
50
9
3
240/416
3
4 wire
50
9
7
380
3
3 wire
60
Note:
Operating voltage must be specified at time of
order. Only the most common voltages are shown above.
X E
E
M
O N
C
M
E N
S
M
P E
S
M
S G
P
M
N 0
A
M
Z
enith
ZTS
Series Ordering Information
Entelli-Switch 250
B 1
Horizongal bypass
unit with MX250
Microprocessor
Control Unit
Example
ZTSCT
0B00040F-ZEC01ZVC40MSTD
This number string shows the correct format
for a ZTS Model Automatic Transfer Switch
with closed transition, an Entelli-Switch
250 microprocessor control unit, Utility -
Generator, 400 amps, 4 pole, NEMA Type 1
enclosure, 120/208V 3
φ
, 4 wire, 60 Hz system
with the standard group of accessories.
*Available only on Bypass configuration
Available for 1600-3000A Non-bypass product ONLY
.
UL
1008
Withstand
and Closing
Ratings
Please refer to
GE
Publication
TB
-1102.
GE D
igital Energy – Power Quality
830
W
40
th Street, Chicago, IL
60609
USA
800 637 1738
www.gepowerquality.com
Information subject to change without notice. Please verify all details with GE.
PB
-
5066 (12/09)
©
20
18
General Electric Company All Rights Reserved
Standard (Open Transition)
Z T S 0 0 0
Z T S D 0 0
Z T S C T 0
Z B T S 0 0
Delayed Transition
Closed Transition
Standard (Open Transition) w/Bypass
Z B T S D 0
Delayed Transition w/Bypass
Z B T S C T
Closed Transition w/Bypass
40 amps
0 0 4
80 amps
0 0 8
100 amps
0 1 0
150 amps
0 1 5
225 amps
0 2 2
260 amps
0 2 6
400 amps
0 4 0
600 amps
0 6 0
800 amps
0 8 0
1000 amps
1 0 0
1200 amps
1 2 0
1600 amps
1 6 0
2000 amps
2 0 0
3000 amps
3 0 0
2600 amps
2 6 0
4000 amps
4 0 0
A
ssembled in the
USA
*
B
4
High withstand panel
with MX250
**
*
*