background image

Zenith ZTS Series Automatic Transfer Switches

Universal Motor
Disconnect (UMD):

This load control discon-
nects a large motor via
its control circuit for an
adjustable period of time
prior to transfer in either
direction. For switching
multiple motors, GE’s

Accessor

y  UMD 

discon-

nects  the  motors  prior

 

to transfer and brings

them back on line
sequentially.

Accessory R50:

This is

an in-phase monitor
that compares the phase
angle between both
sources of power and
prevents transfer until
the two are approximately

in phase (within a self-
adjusting range). GE’s high
speed transfer action,
coupled with the MX
series microprocessor
control logic, ensure 
closures at or near zero
degree phase difference. 

Series ZTSD:

GE

offers

delayed transition
switching on transfer
switches rated 40 amperes
and above – the GE Zenith
ZTSD

Series. This pro-

grammed center-off
position allows for the
full decay of rotating
motors or transformer
fields. It can also be
used for load shedding
of selected circuits or

other applications which
require a means to dis-
connect the load from
either source. Major UPS
system manufacturers
recommend delayed
transition switches for
proper restart sequencing
of their systems.

Series ZTSCT:

GE

’s Zenith

series of closed transition
switches combine ZTSD
operation during a source
failure with a highly
engineered control system
that allows momentary
paralleling (100 ms) of
two acceptable sources,
thereby limiting the
impact of transfer 
on the load.

Electrical Ratings

• Ratings 40 to 4000 amperes

• 2, 3 or 4 Poles

• Open type, NEMA 1, 3R, 4, 4X and 12

• Available to 600 VAC, 50 or 60 Hz

• Suitable for emergency and standby

 

applications on all classes of load,

 

100%

tungsten rated through 400 amps

• UL 1008 listed at 480 VAC

• CSA C22.2 No. 178 certified

 

at 600 VAC

• IEC 947-6-1 listed at 480 VAC

Performance Features

• Contact transfer speed

 

less than

 

100

milliseconds

• High close-in and withstand capability

• Temperature rise test per UL 1008

 

conducted after overload and endurance

 

tests

- exceeds UL requirements

• Available in ZTS (utility-generator), ZTSU

 

(utility-

utility), ZTSG (generator-generator)

 

and ZTSM

(manual) configurations

Design and Construction Features

• Double throw, interlocked operation

• Electrically operated, mechanically held

 

by a 

simple, over-center mechanism

• Segmented silver tungsten alloy

 

contacts

with separate arcing

 

contacts on 225

amp and above

• Arc quenching grids, enclosed arc

 

chambers, and wide contact air gap

 

for 

superior source-to-source isolation

 

on all

units

• Control circuit disconnect plug and

 

drive 

inhibit switch for safe maintenance

• Components accessible for inspection

 

and 

maintenance without removal of

 

the switch 

or power conductors

• Mechanical indicator and contact

 

chamber cover designed for inspection,

 

safety and position designation

Page 3

PB

-5066

The Zenith ZTS Series is the building block of our transfer switch
product line. This ruggedly built power contactor family of switches
has been specifically designed for transfer switch duty with
dependability, versatility and user friendliness of prime concern.

ZTS

switches are available in open type construction for switchboard

installation or nema enclosed to the customer’s specifications. The
power panel components, consisting of power switching contacts,
drive mechanism and terminal lugs, are mounted on a specially
formed panel. Logic devices including microprocessor control
auxiliary time delays and special accessory equipment are
assembled on the door for ease of maintenance and separation
from the power section. They are connected with a numbered
wiring harness equipped with a disconnect plug that allows 
isolation of the control panel for maintenance.

ZTS Series Method of Operation

When Source 1 voltage fails or drops to a predetermined point
(usually 80% of nominal), if required, a circuit is closed to start
the engine generator set. When Source 2 reaches 90% of rated
voltage and 95% of rated frequency, the drive solenoid is energized
through the Source 2 coil control relay, causing the main contacts to
disconnect the load from Source  1 and connect it to Source 2.
After the drive solenoid has completed its electrical stroke and 
is seated, the Source 2 coil control relay opens to disconnect it. The
transfer switch is now mechanically locked in the Source 2 position.

When Source 1 voltage is restored to a predetermined point 
(usually 90% of nominal), the control voltage sensing energizes.
The Source 1 side coil relay closes, and after the drive solenoid
has completed its electrical stroke and is seated, the coil control
relay opens to disconnect it. The transfer switch is now mechanically
locked in the Source 1 position.

Drive Mechanism

All Zenith ZTS

 

switches employ the simple “over-center” principle to

 

achieve a mechanically locked position in either Source 1 or

 

Source 2 and GE’s high speed drive assures contact transfer in

 

100ms or less. High contact pressure and positive mechanical

 

lock allow for high withstand and closing ratings, far exceeding

 

UL

 

requirements. All

 

ZTS

 

units are listed with UL

 time-based 

rating, 

coordinated breaker and current limiting fuse ratings.

Open and Delayed Transition ATS mechanism does not allow 

both sources to be connected at the same time.

Neutral Switching

The Zenith ZTS Series is available in true four pole designs for
multi-source power systems that require neutral switching. The
neutral contact is on the same shaft as the associated main contacts.
This ensures positive operation, and avoids any possibility that
the neutral contact will fail to open or close, as is possible when
the neutral pole is an add-on accessory. The neutral contacts
are identical to the main contacts, having the same current carrying
and high withstand/closing ratings as the mains. They are designed
to break last and make first to reduce the possibility of transients
while switching the neutral.

Safe Manual Operation

The ZTS manual operator consists of a large, easy-to-use handle
that fits securely for manual operation during installation and
maintenance or in an emergency.

The ZTS may be provided with an operator inhibit switch to dis-
connect the electrical drive prior to maintenance. Fully enclosed
wrap-around arc covers shield the main contacts and mechanical
components, preventing operator exposure during manual operation.

Transferring Large Motor or Highly Inductive Loads

Some loads, especially large motors, receive severe mechanical
stress if power is transferred out of phase while the motor is still
rotating. Also, back EMF generated by a motor may result in excess
currents that can blow fuses or trip circuit breakers. GE offers
four solutions to these problems:

Short Time rated 1600-3000A (Non-

bypass) ATS for 0.50 sec and 1.0 sec time 

duration

Open Transition ATS perform break 

before make operation on all phases

Summary of Contents for Zenith ZTS Series

Page 1: ...GE Digital Energy Power Quality Zenith ZTS Series Low Voltage Automatic and Manual Transfer Switches ...

Page 2: ...ed Transition Bypass Switches 100 4000 Amps All ZTS products meet or exceed industry requirements allowing specification and installation confidence UL 1008 listed through 480 VAC CSA C22 2 No 178 listed through 600 VAC IEC 947 6 1 listed through 480 VAC Codes and Standards NFPA 70 99 101 110 IEEE 446 241 602 NEC 517 700 701 702 NEMA ICS 10 Controls tested in accordance with IEEE 472 ANSI C37 90A EN...

Page 3: ...ounted on a specially formed panel Logic devices including microprocessor control auxiliary time delays and special accessory equipment are assembled on the door for ease of maintenance and separation from the power section They are connected with a numbered wiring harness equipped with a disconnect plug that allows isolation of the control panel for maintenance ZTS Series Method of Operation When...

Page 4: ...ommunications allowing connectivity with other ATS s paralleling switchgear and SCADA systems Time tested synchronous logic automatically measures phase angle and frequency allowing disturbance free transfer Unsurpassed statistical ATS System monitoring available in real time T3 W3 elevator pre signal Automatically bypassed if the selected source fails minimizing time an elevator is without power ...

Page 5: ...es and need to be specified AB3 Auxiliary Contact closed in bypass emergency Source 2 S P D T Standard up to 400A Additional available 10 max on ZBTS Series and need to be specified AB4 Auxiliary Contact closed in bypass normal Source 1 S P D T Standard up to 400A Additional available 10 max on ZBTS Series and need to be specified CALIBRATE Microprocessor activated calibration feature CDP Programm...

Page 6: ... 1 R1 3 Over Voltage sensing for normal Source 1 single R1 1 or three R1 3 phase R15 R15D Load Shed Should Source 2 become overloaded an external signal can be given to ATS to transfer to the Neutral or dead Normal Source 1 position R16 Phase rotation sensing of Normal Source 1 and Emergency Source 2 R50 In Phase monitor between Normal Source 1 and Emergency Source 2 to allow transfer S5P Micropro...

Page 7: ...14 HxWxD For 260 400A the enclosure is 66 x 24 x 19 75 HxWxD For 600A the enclosure is 74 x 40 x 19 75 HxWxD For certified drawings please contact the GE factory Application Notes NOTES Line and load terminals are located in rear and arranged for bus bar connection Terminal lugs are available as an accessory Contact the GE factory for more details 1 Special terminal lugs and neutral bars are availa...

Page 8: ...0 1 3 wire 50 5 7 480 1 2 wire 60 5 8 254 440 3 4 wire 60 6 0 575 3 3 wire 60 6 1 347 600 3 4 wire 60 6 3 575 1 2 wire 60 7 0 277 480 3 4 wire 60 7 1 277 1 2 wire 60 7 4 266 460 3 4 wire 60 7 5 460 3 3 wire 60 8 2 380 1 2 wire 50 9 0 240 416 3 4 wire 60 9 1 220 380 3 4 wire 60 9 2 220 380 3 4 wire 50 9 3 240 416 3 4 wire 50 9 7 380 3 3 wire 60 Note Operating voltage must be specified at time of or...

Reviews: