2-72
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
6108
87PC Received Volts Channel 1
0 to 125
V
0.1
F001
120
"
6109
87PC Received Volts Channel 2
0 to 125
V
0.1
F001
120
"
610A
87PC High-Speed Contact 1
0 to 64
---
1
F490
0
"
610B
87PC High-Speed Contact 2
0 to 64
---
1
F490
0
"
610C
87PC FDL AUX
0 to 4294967295
---
1
F300
0
"
610E
87PC FDH AUX
0 to 4294967295
---
1
F300
0
"
6110
87PC Reset Delay
0 to 200
ms
1
F001
30
"
6111
87PC Mixed Signal Reference Angle
0 to 359
°
1
F001
0
"
6112
87PC Trip Security
0 to 1
---
1
F534
0 (First
Coincidence)
"
6113
87PC Second Coincidence Timer
10 to 200
ms
1
F001
40
"
6114
87PC Enhanced Stability Angle
40 to 180
°
5
F001
110
"
6115
87PC FDH Supervision
0 to 4294967295
---
1
F300
0
"
6117
87PC Pickup Delay
0 to 50
ms
1
F001
0
"
6118
87PC Stop Tx
0 to 4294967295
---
1
F300
0
"
611A
87PC Tx Reset Delay
0 to 1000
ms
1
F001
0
Continuous Monitor (Read/Write Setting)
L90
6130
Continuous Monitor Function
0 to 1
---
1
F102
0 (Disabled)
"
6131
Continuous Monitor I (current) OP
0 to 4294967295
---
1
F300
0
"
6133
Continuous Monitor I (current) Supervision 0 to 4294967295
---
1
F300
0
"
6135
Continuous Monitor V (voltage) OP
0 to 4294967295
---
1
F300
0
"
6137
Continuous Monitor V (voltage) Supervision 0 to 4294967295
---
1
F300
0
"
6139
Continuous Monitor Target
0 to 2
---
1
F109
0 (Self-reset)
"
613A
Continuous Monitor Events
0 to 1
---
1
F102
0 (Disabled)
Transformer Hottest Spot (Read/Write Grouped Setting)
T60
6140
Transformer Hottest Spot Function
0 to 1
---
1
F102
0 (Disabled)
"
6141
Transformer Hottest Spot Pickup
50 to 300
°C
1
F001
140
"
6142
Transformer Hottest Spot Delay
0 to 30000
min
1
F001
1
"
6143
Transformer Hottest Spot Block
0 to 4294967295
---
1
F300
0
"
6145
Transformer Hottest Spot Target
0 to 2
---
1
F109
0 (Self-reset)
"
6146
Transformer Hottest Spot Events
0 to 1
---
1
F102
0 (Disabled)
Transformer Aging Factor (Read/Write Grouped Setting)
T60
6150
Transformer Aging Factor Function
0 to 1
---
1
F102
0 (Disabled)
"
6151
Transformer Aging Factor Pickup
1 to 10
PU
0.1
F001
20
"
6152
Transformer Aging Factor Delay
0 to 30000
min
1
F001
10
"
6153
Transformer Aging Factor Block
0 to 4294967295
---
1
F300
0
"
6155
Transformer Aging Factor Target
0 to 2
---
1
F109
0 (Self-reset)
"
6156
Transformer Aging Factor Events
0 to 1
---
1
F102
0 (Disabled)
Transformer Loss of Life (Read/Write Grouped Setting)
T60
6160
Transformer Loss of Life Function
0 to 1
---
1
F102
0 (Disabled)
"
6161
XFMR LOL Initial Value
0 to 500000
hrs
1
F003
0
"
6163
Transformer Loss of Life Pickup
0 to 500000
hrs
1
F003
180000
"
6165
Transformer Loss Of Life Block
0 to 4294967295
---
1
F300
0
"
6167
Transformer Loss of Life Target
0 to 2
---
1
F109
0 (Self-reset)
"
6168
Transformer Loss of Life Events
0 to 1
---
1
F102
0 (Disabled)
Transformer Thermal Inputs (Read/Write Setting)
T60
6170
Transformer Thermal Model Source Input
0 to 5
---
1
F167
0 (SRC 1)
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...