E
The Fault Report element has been enhanced to accommodate neutral current values
Products: C60, D30, D60, F35, F60, L30, L60, L90
Corrected firmware: 5.80
Description: The Fault Report element is now able to capture and show pre-fault and fault phasors
(magnitude and angle values) of the neutral current. This implementation makes analysis of fault events
easier.
GE tracking number: 580-22
N New self-test FlexLogic operand has been added to indicate a “Brick Trouble” condition
Products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L90, M60, N60, T35, T60
Corrected firmware: 5.80
Description: “Brick Trouble” is a self-reset minor self-test warning message available on UR devices when
configured with the IEC61850 Process Bus module (HardFiber Brick). The message activates the “Any self-
tests” and “Any minor error” operands. With firmware version 5.80, a new operand “Brick Trouble” has
been created to specifically identify this self-test alarm. Like any other FlexLogic operand, this new
operand is available to be used across the full range of protection and control elements (FlexLogic, digital
elements, and so on).
GE tracking number: 580-23