Smoke Sensor 868 GEN2

Installation Instructions

4

Note:  

The control panel alarm and all auxiliary functions should be 

verified for a complete test of the system.

Smoke sensor limitations

Smoke sensors may not work under all conditions. Smoke 
sensors cannot provide total protection of life or property and are 
not a substitute for insurance. All smoke sensors are subject to 
possible compromise or failure-to-warn for a variety of reasons. 
For example:

• This smoke sensor will not operate and an alarm will not 

sound if its batteries are dead, removed, or not installed 
correctly.

• Radio signals transmitted by this smoke sensor may be 

blocked or reflected by metal objects. Adjacent devices or 
systems using radio frequency signals may interfere with 
the operation of this smoke sensor. Test the system weekly 
to ensure signals are transmitted and received properly.

• Closed or partially closed doors and distance can block or 

reduce the alarm sound from this smoke sensor. This smoke 
sensor is not designed for the hearing impaired.

• Smoke sensors cannot detect smoke inside chimneys, walls, 

roofs, or smoke blocked by a closed door.

• Smoke sensors may not detect smoke on other levels of the 

building.

• Smoke sensors may not warn in time when fires are caused 

by smoking in bed, explosions, improper storage of flamma-
bles, overloaded electrical circuits, or other hazardous 
conditions.

Specifications

 

 

Model number

TX-6211-03-1, RF6211-03-1

RF frequency

868 MHz

Compatibility

GE Security 868 GEN2 control panels/

receivers

Battery type

Two 3.0 V, 1300 mAh Lithium

Recommended batteries

Duracell DL 123A, Panasonic CR123A, Sanyo 

CR123A

Typical standby current

35 µA

Estimated battery life

Four to six years (at 20°C)

Supervisory interval

64 minutes

Typical RF output power

12 mW

Sounder (temporal pattern)

85 dBa at 3 m

Smoke sensor sensitivity

2.2% ± 1.3%/3 dm

RF immunity

20 V/m minimum, 0 to 1000 MHz

Heat detector specifications
   Rate-of-rise
   Fixed

15°F/min > 105°F (8.3°C/min > 40.6°C)
135°F ± 5°F) (57.2°C ± 2.8°C)

Operating temperature

40 to 100°F (4.4 to 37.8°C)

Storage temperature

4 to 167°F (-20 to 75°C)

Relative humidity range

0 to 95% noncondensing

Dimensions (L x W x H)

5.6 x 5.6 x 2.5 in. (141 x 141 x 63 mm)

Weight

288 g

Technical support

888 GE Security (888.437.3287). Toll-free in the US, Puerto Rico, and Canada. 

503.885.5700 outside the toll-free area or contact your local dealer. 

www.gesecurity.com

  

   

 

Summary of Contents for TX-6211-03-1

Page 1: ...mounted smoke sensors in the center of the room or hallway at least 4 in 10 cm away from any walls or partitions When mounting to suspended ceiling tile the tile must be secured with the appropriate fastener to prevent removal Do not mount the smoke sensor to the metal runners of suspended ceiling grids The metal runners can draw the magnet s field away from the smoke sensor s reed switch causing ...

Page 2: ...d mark the mounting holes 3 Secure the mounting base to the surface using appropriate hardware 4 Attach the smoke sensor to the mounting base Testing Test the smoke sensor using the following tests Sensor test Smoke test Sensitivity test Sensor test The sensor test verifies good communication between the panel and the smoke sensor To do a sensor test refer to your panel documentation and do the fo...

Page 3: ...e instructions and or instructions from local government authorities 4 Observing correct polarity insert two new batteries into the battery compartment and replace the battery cover 5 Attach the smoke sensor to the mounting base and test the system Maintenance Clean the smoke sensor cover with a dry or damp water cloth as needed to keep it free from dust and dirt When necessary clean the smoke sen...

Page 4: ...roofs or smoke blocked by a closed door Smoke sensors may not detect smoke on other levels of the building Smoke sensors may not warn in time when fires are caused by smoking in bed explosions improper storage of flamma bles overloaded electrical circuits or other hazardous conditions Specifications Model number TX 6211 03 1 RF6211 03 1 RF frequency 868 MHz Compatibility GE Security 868 GEN2 contr...

Reviews: