GE TX-6211-03-1 Installation Instructions Download Page 3

3

Sensitivity test

To test the smoke sensor sensitivity, do the following:

1.

Press and hold the smoke sensor test button for two seconds, 
then release it. The smoke sensor transmits a test signal, and 
then does a self-test that causes the LED to flash one to nine 
times.

2.

Count the number of LED flashes, then use 

Table 1

 to deter-

mine if any action is needed.

Fault conditions

Correct fault conditions as soon as possible. The smoke sensor 
indicates a fault condition in the following ways:

• The LED stops working (no flashing or turning on) if the 

smoke sensor sensitivity is not within the normal range, or if 
an unserviceable hardware fault is detected.

• The smoke sensor stops transmitting supervisory signals if 

the smoke sensor has an unserviceable hardware fault or is 
not sensitive enough, causing the panel to indicate the 
smoke sensor is in a supervisory condition. However, the 
smoke sensor can still transmit alarm signals.

• The smoke sensor transmits a trouble (CleanMe) signal 

when the smoke sensor is too sensitive. The panel 
announces “Sensor 

number

name

, open or fire warning”. 

Battery replacement

When the battery voltage gets low, the smoke sensor transmits a 
low battery signal to the panel. The panel activates trouble beeps 
through system sirens and identifies the smoke sensor with the 
low battery. If batteries are not replaced within seven days, the 
smoke sensor’s built-in sounder emits a short beep of chirp every 
45 seconds. You can silence smoke sensor chirps for 24 hours by 
pressing the smoke sensor’s test button. Replace low batteries as 
soon as possible. Use only 3-volt lithium batteries listed in 

Spec-

ifications

 on page 4.

To replace the batteries, do the following:

1.

Remove the smoke sensor from the mounting base.

2.

Slide the battery compartment cover away from the smoke 
sensor to unsnap it and lift it off (

Figure 1

 on page 1).

3.

Remove the batteries and dispose of them according to 
battery directive instructions and/or instructions from local 
government authorities.

4.

Observing correct polarity, insert two new batteries into the 
battery compartment and replace the battery cover.

5.

Attach the smoke sensor to the mounting base and test the 
system.

Maintenance

Clean the smoke sensor cover with a dry or damp (water) cloth as 
needed to keep it free from dust and dirt. When necessary, clean 
the smoke sensor interior and replace the optical chamber (part 
211).

To replace the optical chamber, do the following:

1.

Contact the central monitoring station and inform them that 
you will be doing maintenance to the system.

2.

Remove the smoke sensor from the mounting base and 
remove the batteries.

3.

Slide a flat-bladed screwdriver in the slot on the smoke 
sensor cap and gently push the handle down to pry off the 
smoke sensor cap (

Figure 3

).

Figure 3. Removing the smoke sensor cap

4.

Squeeze the optical chamber and pull it up and away from 
the optical base and discard (

Figure 4

).

Figure 4. Optical chamber

5.

Blow out or use a soft-bristled brush to remove all dust and 
dirt from the optical base.

6.

Line up the new optical chamber with the optical base and 
snap both side of the optical chamber into place.

7.

To replace the smoke sensor cap, line up the cap with the 
smoke sensor, insert the cap, and turn the cap approximately 
15 degrees. It should snap firmly into place.

8.

Observing proper polarity, install batteries and replace the 
battery cover.

9.

Attach the smoke sensor to the mounting base and test 
smoke sensor sensitivity.

Table 1.

Sensitivity test

Flashes

Indication/action

1

Unserviceable hardware fault detected. Reset the unit by 

removing and replacing the batteries and retest. If error 

persists, replace the unit.

2 to 3

Unit is becoming insensitive. Clean the unit. Reset the unit 

by removing and replacing the batteries and retest. If error 

persists, replace the unit.

4 to 7

Unit is within normal range. No action needed.

8 to 9

Unit is becoming too sensitive. Verify that the smoke 

chamber is snapped down securely. Clean the unit. Replace 

the optical chamber (part 211)

Smoke sensor cap

Optical chamber

Smoke sensor

Optical base

Summary of Contents for TX-6211-03-1

Page 1: ...mounted smoke sensors in the center of the room or hallway at least 4 in 10 cm away from any walls or partitions When mounting to suspended ceiling tile the tile must be secured with the appropriate fastener to prevent removal Do not mount the smoke sensor to the metal runners of suspended ceiling grids The metal runners can draw the magnet s field away from the smoke sensor s reed switch causing ...

Page 2: ...d mark the mounting holes 3 Secure the mounting base to the surface using appropriate hardware 4 Attach the smoke sensor to the mounting base Testing Test the smoke sensor using the following tests Sensor test Smoke test Sensitivity test Sensor test The sensor test verifies good communication between the panel and the smoke sensor To do a sensor test refer to your panel documentation and do the fo...

Page 3: ...e instructions and or instructions from local government authorities 4 Observing correct polarity insert two new batteries into the battery compartment and replace the battery cover 5 Attach the smoke sensor to the mounting base and test the system Maintenance Clean the smoke sensor cover with a dry or damp water cloth as needed to keep it free from dust and dirt When necessary clean the smoke sen...

Page 4: ...roofs or smoke blocked by a closed door Smoke sensors may not detect smoke on other levels of the building Smoke sensors may not warn in time when fires are caused by smoking in bed explosions improper storage of flamma bles overloaded electrical circuits or other hazardous conditions Specifications Model number TX 6211 03 1 RF6211 03 1 RF frequency 868 MHz Compatibility GE Security 868 GEN2 contr...

Reviews: