Power Supply Features

(GEPS24D-80U)

• Supports Tetra PowerStrip DS, Tetra miniStrip DS, Tetra EdgeStrip, 

  Tetra Contour and Tetra Contour LS LED lighting systems

• Compatible with 0-10V Dimming controller

• Class 2 wiring per NEC Article 725

• Damp location rated

• IP66 rated: separate enclosure required

Connect the supply wire that 

is attached to the Tetra LED 

System to the red (+) and black (-) 

output wires of the power supply 

as outlined in the “

Electrical 

Connections

” section of your LED 

system’s 

Installation Instructions.

1

Connect the AC line to the black 

(line) and white (neutral) input 

wires of the power supply using 

18-14 AWG (0.82-2.08 mm

2

or 18-10 AWG (0.82-5.26mm

2

twist-on wire connectors. 

Properly ground power supply in 

accordance with National Electric 

Code (NEC) Article 600.

3

Tetra

®

 

LED Systems Power Supply

Connect the (+) purple and (-) gray 

wires of the Tetra Dimming Power 

Supply to the 0-10V dimming 

controller. Refer to the dimming 

controller installation instructions for 

specific connection information.

2

GE

Lighting Solutions

Installation Guide

24

Volt

To Tetra LED System

To Dimming 

controller

Output 

wires

White (neutral)

Black (line)

Red (+)

Black (-)

AC line

To Tetra LED System

Purple (+)

Purple (+)

Gray (-)

Gray (-)

Dimming 

controller

RISK OF ELECTRIC SHOCK:

• Disconnect power at fuse box or circuit breaker before servicing or  

  installing product.
• Properly ground Tetra

®

 power supply.

RISK OF FIRE:

• Use only Tetra

®

 supply wire to make connection from Tetra

®

 power  

  supply to Tetra

®

 LED strip.

• Use only approved wire for input/output connection. 

  Minimum size 18 AWG (0.82mm

2

)

• Follow all NEC and local codes.

RISQUES DE DÉCHARGES ÉLECTRIQUES

• Coupez l’alimentation électrique à la boîte de fusibles ou au    

  disjoncteur avant l’entretien ou l’installation du produit.
• Assurez-vous de correctement mettre à terre l’alimentation    

  électrique Tetra

®

.

RISQUES D’INCENDIE

• N’utilisez que le fil d’approvisionnement Tetra® pour faire la    

  connexion entre l’alimentation Tetra

®

 et la bande DEL Tetra

®

.

• N’utilisez que des fils approuvés pour les entrées/sorties de    

  connexion. Taille minimum 18 AWG (0.82mm

2

).

• Respectez tous les codes NEC et codes locaux.

BEFORE YOU BEGIN

Read these instructions completely and carefully.

WARNING/AVERTISSEMENT

Power Supply Installation