NOTE: 

For installation in Canada, a disconnect switch of appropriate rating needs to be placed within 29.5 ft. (9 m) of primary side of 

the power supply. The switch voltage rating shall not be less than the branch circuit voltage. The switch must also support twice the 

amount of input current.

NOTE: 

When installing power supply, connect to the appropriate sized building breaker or disconnect device for line, neutral and 

ground connections, in accordance with National Electric Code (NEC) Article 600 and all local regulations.

NOTE: 

Exceeding maximum load per bank will cause the LEDs to dim or blink. Once the excess load is removed, cycle the input power 

to restart the power supply.

1.  (Existing Signs Only) Prior to installation, survey the site for information regarding power and accessibility inside and outside the   

 

  building. Ensure that the branch circuit supplying the existing transformer or ballast will be within the voltage ratings of the new  

 

  LED power supply, and have a current rating not exceeding 20A, or that permitted by applicable local, state, or country electrical codes   

  (whichever is less). 

2.  (Existing Signs Only)

 

 

 

NOTE:

3.  (Existing Signs Only) If removal of the existing lighting equipment eliminates the disconnect switch, as required by applicable local,    

  state, or country electrical codes; a new disconnect switch must be installed.

4.  (Existing Signs Only) Make sure the removal of lighting equipment does not compromise the integrity of the sign body (i.e. water   

 

  intrusion). Fill in all holes 0.5 in. (13 mm) or smaller with the appropriate amount of rated caulk or sealant. For holes greater than  

 

  0.5 in. (13 mm), use an aluminum or zinc coated steel patch with rivets and sealant.

5.  Using the layout guidelines within the LED module installation instructions, determine required number of LED modules required to    

  illuminate the sign.

6.  Using the applicable LED module maximum Loading chart, determine the number of Tetra Class 2 Power Supplies required to power the  

  number of LED modules required to illuminate the sign, so as not to overload any single power supply output.

7.  Follow the LED module instructions to properly mount the LED modules. 

8.  Connect the DC output of the power supply to the LED modules using the Power Supply Installation instructions above.

9.  Connect AC power to the power supply in accordance with the applicable local, state, and country electrical codes, and the Power     

  Supply Installation instructions above.

10. 

 

 

  electrical codes.

Connect the supply wire that is 

attached to the Tetra LED System to 

the red (+) and black (-) output wires 

of the power supply as outlined in 

the “Electrical Connections” section 

of your LED system’s Installation 

Instructions.

NOTE:

 Three 96 watt output 

banks per power supply. Do not 

interconnect output terminations.

2

Mount power supply and remove 

junction box cover. Carefully 

remove knockout for AC line input 

wires. Install appropriate electrical 

wire protection. 

Connect the AC line to the black (line) 

and white (neutral) input wires of 

the power supply and connect the 

branch circuit ground to the green 

wire with a yellow stripe (ground) wire 

using appropriately sized twist-on 

wire connectors.

1

3

To Tetra LED System

Output wires

Power Supply Installation

White 

(neutral)

Black 

(line)

Green with yellow stripe (ground)

AC line