Step 6: Combine the zip ties to make a loop and install zip ties around top set of breakers in panel as shown in picture below. Pull on
ends to make tight around breakers. Trim zip ties as needed and install Warning label next to release tab on zip tie at
generator breaker.
Step 7: Re-Install panel cover, Verify proper operation of interlock. Main breaker
ON,
generator breaker
OFF
and generator breaker
CAN NOT
be turned on. Generator breaker
ON
, main breaker
OFF
and main breaker
CAN NOT
be turned on.
Main On
Generator On
Place Generator start-up procedure label on panel box, Place CAUTION label on panel box and electric meter pan.
The MAIN and the GENERATOR breakers should NEVER be able to be turned on at the same time. If panel cover is removed the
Generator breaker is NEVER to be turned on. If for any reason the interlock does not function properly, DO NOT USE and contact us
immediately at
for support and instructions.