GE RSEN-WLV Installation Instructions Manual Download Page 3

Catalog Number: RSEN-WLV

3

YELLOW

RED

BLACK

WHITE

1

24V

RECT

BLUE

24V

RECT

BLUE

YELLOW

RED

BLACK

WHITE

YELLOW

RED

BLACK

WHITE

YELLOW

RED

BLACK

WHITE

1

2

3

#20/3 AWG

1000 FEET MAXIMUM

RSWIRE-3 (standard class)

RSWIRE-3P (plenum applications)

Note: Relays 1, 2, 3 and 4 are now permanently
wired as a group. You can’t control them individually.
Maximum of 3 relays in parallel.

YELLOW

RED

BLACK

WHITE

4

SENSOR CONTROL OF A GROUP OF RELAYS

ON/OFF SENSOR CONTROL

#20/3 AWG

1000 FEET MAXIMUM

RSWIRE-3 (standard class)

RSWIRE-3P (plenum applications)

INSTALLATION (CONTINUED)

Checkout and Adjustment

Once installation is complete, restore power to the lighting
circuit. Proper operation of the RSEN-WLV must be verified.
Adjustments should be made with the HVAC system on.

Use only insulated tools to make adjustments.

1. Adjustment controls are under the touchplate. Release the

touchplate by depressing the latch at the top. “Time Delay”
ranges from 15 seconds (for testing) to 30 minutes. Using a
small screwdriver, set “Time Delay” to 15 seconds by
turning the control completely counterclockwise until it
stops at minimum setting (approximately 8 o’clock). Turn
control for “Area Range” until flat edge of control is at 10
o’clock. Turn “Entry Range” until flat edge of control is at 9
o’clock.

2. Move the “Mode” switch to the “Auto” or “A” position.
3. The area of coverage can be determined by watching the

LED indicator on the front of the sensor while moving
around the room. The LED lights only when the sensor
detects motion. Adjust the “Area Range” control to the
lowest setting that provides adequate motion detection of
a person working in the room. Do not set higher than
necessary.

4. Leave the room. The lights should go out in approximately

15 seconds. Wait at least 12 seconds after the lights go
out. Walk normally back into the room and verify that the
lights turn on automatically. If not, the “Entry Range”
should be increased slightly. Do not set higher than
necessary.

5. If the LED blinks when there is no movement in the room, it

is possible that the sensor is being activated by air flow
from the HVAC system. Reduce the “Area Range” setting
until the LED goes off and stays off with no motion.

6. If the sensor is activated by passers-by in the hallway,

reduce the “Entry Range” setting.

7. Set “Time Delay” to the desired setting for normal use. If

lights go out while the room is occupied, increase setting
slightly until an optimum interval is obtained. Recom-
mended time delay is usually 6-8 minutes (approximately
12-1 o’clock). People who remain very still for long periods
may need a longer time delay.

8. If preferred, the RSEN-WLV may be set to Manual ON for

maximum energy savings by moving the “Mode” switch to
the “M” position. In this setting, the occupant must push
the touchplate to turn on lights upon entering the room.

Area

Entry

Time

Delay

1/4         30

Range

M        A

Switch to 

M

 for Manual On

Switch to 

A

 for Auto On

Sensitivity

Adjustments,

clockwise

minimum

to

maximum

Time Delay

Adjustment,

clockwise

15 seconds

to

30 minutes

Sensor Adjustment

Sensor Wiring To A TLC Relay Panel

Sensor Wiring

RSEN-WLV

RED

WHITE

RED

BLUE

BLACK

BLACK

* NOTE: USE ONLY 

GE RR SERIES RELAYS

24 VAC

RR SERIES*
RELAY

TO
ADDITIONAL
RELAYS
(OPTIONAL)
4 MAXIMUM

NEUTRAL

HOT

LINE

LOAD

Summary of Contents for RSEN-WLV

Page 1: ...e room When no motion is detected the lights will turn off automatically after the pre set time delay Following this a grace period of approximately ten seconds allows lights to be turned on again by motion At any time lights may be turned off while the room is occupied by pressing the touchplate The RSEN WLV is fully self resetting lights turned off manually in Automatic ON mode will stay off whi...

Page 2: ...iently located junction box Alternative Relay Location The RSEN WLV may be wired back to a GE TLC relay panel in the elecrical closet using low voltage wiring This is especially useful in retrofit situations where the sensor replaces an existing low voltage wall switch Note The RSEN WLV is NOT compatible with the terminals of the GE Softwired Switching System as four wires are required to draw pow...

Page 3: ... Range control to the lowest setting that provides adequate motion detection of a person working in the room Do not set higher than necessary 4 Leave the room The lights should go out in approximately 15 seconds Wait at least 12 seconds after the lights go out Walk normally back into the room and verify that the lights turn on automatically If not the Entry Range should be increased slightly Do no...

Page 4: ...hts do not turn on after pressing the touchplate confirm that no other switches or equipment are interrupt ing or bypassing power to the relay transformer or load Disconnect the white wire from the transformer Wait 5 seconds and reconnect The relay should close on application of power and motion detection If the relay does not close check the wiring Momentarily short the relay control leads Red to...

Reviews: