Catalog Number: RSEN-WLV
3
YELLOW
RED
BLACK
WHITE
1
24V
RECT
BLUE
24V
RECT
BLUE
YELLOW
RED
BLACK
WHITE
YELLOW
RED
BLACK
WHITE
YELLOW
RED
BLACK
WHITE
1
2
3
#20/3 AWG
1000 FEET MAXIMUM
RSWIRE-3 (standard class)
RSWIRE-3P (plenum applications)
Note: Relays 1, 2, 3 and 4 are now permanently
wired as a group. You can’t control them individually.
Maximum of 3 relays in parallel.
YELLOW
RED
BLACK
WHITE
4
SENSOR CONTROL OF A GROUP OF RELAYS
ON/OFF SENSOR CONTROL
#20/3 AWG
1000 FEET MAXIMUM
RSWIRE-3 (standard class)
RSWIRE-3P (plenum applications)
INSTALLATION (CONTINUED)
Checkout and Adjustment
Once installation is complete, restore power to the lighting
circuit. Proper operation of the RSEN-WLV must be verified.
Adjustments should be made with the HVAC system on.
Use only insulated tools to make adjustments.
1. Adjustment controls are under the touchplate. Release the
touchplate by depressing the latch at the top. “Time Delay”
ranges from 15 seconds (for testing) to 30 minutes. Using a
small screwdriver, set “Time Delay” to 15 seconds by
turning the control completely counterclockwise until it
stops at minimum setting (approximately 8 o’clock). Turn
control for “Area Range” until flat edge of control is at 10
o’clock. Turn “Entry Range” until flat edge of control is at 9
o’clock.
2. Move the “Mode” switch to the “Auto” or “A” position.
3. The area of coverage can be determined by watching the
LED indicator on the front of the sensor while moving
around the room. The LED lights only when the sensor
detects motion. Adjust the “Area Range” control to the
lowest setting that provides adequate motion detection of
a person working in the room. Do not set higher than
necessary.
4. Leave the room. The lights should go out in approximately
15 seconds. Wait at least 12 seconds after the lights go
out. Walk normally back into the room and verify that the
lights turn on automatically. If not, the “Entry Range”
should be increased slightly. Do not set higher than
necessary.
5. If the LED blinks when there is no movement in the room, it
is possible that the sensor is being activated by air flow
from the HVAC system. Reduce the “Area Range” setting
until the LED goes off and stays off with no motion.
6. If the sensor is activated by passers-by in the hallway,
reduce the “Entry Range” setting.
7. Set “Time Delay” to the desired setting for normal use. If
lights go out while the room is occupied, increase setting
slightly until an optimum interval is obtained. Recom-
mended time delay is usually 6-8 minutes (approximately
12-1 o’clock). People who remain very still for long periods
may need a longer time delay.
8. If preferred, the RSEN-WLV may be set to Manual ON for
maximum energy savings by moving the “Mode” switch to
the “M” position. In this setting, the occupant must push
the touchplate to turn on lights upon entering the room.
Area
Entry
Time
Delay
1/4 30
Range
M A
Switch to
M
for Manual On
Switch to
A
for Auto On
Sensitivity
Adjustments,
clockwise
minimum
to
maximum
Time Delay
Adjustment,
clockwise
15 seconds
to
30 minutes
Sensor Adjustment
Sensor Wiring To A TLC Relay Panel
Sensor Wiring
RSEN-WLV
RED
WHITE
RED
BLUE
BLACK
BLACK
* NOTE: USE ONLY
GE RR SERIES RELAYS
24 VAC
RR SERIES*
RELAY
TO
ADDITIONAL
RELAYS
(OPTIONAL)
4 MAXIMUM
NEUTRAL
HOT
LINE
LOAD