GE RSEN-WLV Installation Instructions Manual Download Page 2

Catalog Number: RSEN-WLV

2

INSTALLATION

Coverage

The RSEN-WLV is designed for offices or small rooms up to
300 square feet. Although total coverage of minor motion is
450 square feet, wall switches are normally mounted off-center
in a room which reduces the coverage attainable.

Basic Installation Steps

1. Turn off power at the circuit breaker.
2. Wire and mount the switch in standard junction box.
3. Restore power to the circuit.
4. Adjust settings and test.

Location

Wall switch:

 When installing the RSEN-WLV in a new

junction box, choose the switch location carefully to provide
optimum coverage of the occupied area. When replacing an
existing wall switch, bear in mind that there must be a clear
line of sight between the sensor and the area to be covered.
Avoid pointing the switch directly into the hallway where it
may detect passers-by.

Relay and transformer:

 (Note: Use only GE RR series

relays.) The relay and transformer are generally mounted
above the ceiling on a junction box that contains a hot line,
neutral and exisitng switch leg from which the lighting is
controlled. If additional relays are required, they are mounted
in the box that contains the appropriate switch leg. In
installations whare there are no existing switch legs, the
relay and transformer may be mounted in a conveniently
located junction box.

Alternative Relay Location:

 The RSEN-WLV may be wired

back to a GE TLC relay panel in the elecrical closet using low-
voltage wiring. This is especially useful in retrofit situations,
where the sensor replaces an existing low-voltage wall
switch.

Note: The RSEN-WLV is NOT compatible with the terminals of
the GE Softwired Switching System, as four wires are
required to draw power for the sensor from this particular
panel model. Use the RSENSOR-x series of ceiling sensors
instead.

SENSOR

25 (7.6)

20

(6.1)

24

(7.3)

30 (9.1)

feet (meters)

MOTION-AT-DESK COVERAGE

1

2

 STEP WALK COVERAGE

Sensor Coverage

Sensor Location

S

10' x 15OFFICE

Mounting

CAUTION: Before installing or performing any service
on an RSEN-WLV, power must be turned off at the
circuit breaker panel.

The RSEN-WLV can replace one switch in any standard single
or double gang box. It may be installed in the same manner as
any 3-wire low-voltage wall switch. Wire the RSEN-WLV as
described in the wiring section below.

Wiring

CAUTION: The RSEN-WLV is for use with 24 VAC only.
Do not use with any other voltage. Do not wire to control
receptacle circuits.

Up to four GE RR-type relays may be connected to any one
RSEN-WLV sensor switch.

RSEN-WLV is provided with Teflon-insulated pigtails. The
components are interconnected using #18 AWG Class 2
wiring per NEC 725. Use UL-recognized Teflon-insulated wire
approved for plenum areas per NEC 725-2(b) where required.
Wire RSEN-WLV, the relay, transformer and load as shown.

Summary of Contents for RSEN-WLV

Page 1: ...e room When no motion is detected the lights will turn off automatically after the pre set time delay Following this a grace period of approximately ten seconds allows lights to be turned on again by motion At any time lights may be turned off while the room is occupied by pressing the touchplate The RSEN WLV is fully self resetting lights turned off manually in Automatic ON mode will stay off whi...

Page 2: ...iently located junction box Alternative Relay Location The RSEN WLV may be wired back to a GE TLC relay panel in the elecrical closet using low voltage wiring This is especially useful in retrofit situations where the sensor replaces an existing low voltage wall switch Note The RSEN WLV is NOT compatible with the terminals of the GE Softwired Switching System as four wires are required to draw pow...

Page 3: ... Range control to the lowest setting that provides adequate motion detection of a person working in the room Do not set higher than necessary 4 Leave the room The lights should go out in approximately 15 seconds Wait at least 12 seconds after the lights go out Walk normally back into the room and verify that the lights turn on automatically If not the Entry Range should be increased slightly Do no...

Page 4: ...hts do not turn on after pressing the touchplate confirm that no other switches or equipment are interrupt ing or bypassing power to the relay transformer or load Disconnect the white wire from the transformer Wait 5 seconds and reconnect The relay should close on application of power and motion detection If the relay does not close check the wiring Momentarily short the relay control leads Red to...

Reviews: