GE RSEN-WLV Installation Instructions Manual Download Page 1

Catalog Number: RSEN-WLV

1

DESCRIPTION AND OPERATION

Low-voltage Wall Switch Occupancy Sensor

Total Lighting Control

Installation Instructions

IMRSEN-WLV

FEATURES

The RSEN-WLV is a self-contained motion-sensing
lighting control which replaces a low-voltage wall
switch for energy savings and convenience. Lights turn
off automatically after a room is vacated.

Built-in sensors produce low intensity, inaudible sound and
detect changes in sound waves caused by motion, such as
walking into the room, reaching for a telephone, turning in a
chair. The sensor does not respond to audible sound.

In the Automatic ON mode, the lights turn on automatically
when a person enters the room. In the Manual ON mode,
lights are turned on by pressing the touchplate on the switch.
Modes can be changed by flipping the concealed switch under
the touchplate. In either mode, lights will remain on as long
as motion is detected in the room. When no motion is detected,
the lights will turn off automatically after the pre-set time
delay. Following this, a “grace period” of approximately ten
seconds allows lights to be turned on again by motion.

At any time, lights may be turned off while the room is
occupied by pressing the touchplate. The RSEN-WLV is fully
self-resetting; lights turned off manually in Automatic ON
mode will stay off while the room remains occupied. After the
room is vacated and the preset time delay and grace period
have elapsed, the lights will remain off until turned on
automatically the next time someone enters the room.

The RSEN-WLV can be used with a standard toggle switch to
split the lighting load for rooms that are wired for two
switches as shown in the wiring diagram.

• Replaces a low-voltage wall switch
• For use in small rooms or offices up to 300 square feet
• For use with 24 VAC only
• Choice of automatic ON or manual ON modes
• Separate time delay and sensitivity adjustments
• For indoor use only

Before proceeding, read the enclosed installation
instructions. For GE TLC Service, call: 1-8

77-584-2685

(USA) and (Canada).

Summary of Contents for RSEN-WLV

Page 1: ...e room When no motion is detected the lights will turn off automatically after the pre set time delay Following this a grace period of approximately ten seconds allows lights to be turned on again by motion At any time lights may be turned off while the room is occupied by pressing the touchplate The RSEN WLV is fully self resetting lights turned off manually in Automatic ON mode will stay off whi...

Page 2: ...iently located junction box Alternative Relay Location The RSEN WLV may be wired back to a GE TLC relay panel in the elecrical closet using low voltage wiring This is especially useful in retrofit situations where the sensor replaces an existing low voltage wall switch Note The RSEN WLV is NOT compatible with the terminals of the GE Softwired Switching System as four wires are required to draw pow...

Page 3: ... Range control to the lowest setting that provides adequate motion detection of a person working in the room Do not set higher than necessary 4 Leave the room The lights should go out in approximately 15 seconds Wait at least 12 seconds after the lights go out Walk normally back into the room and verify that the lights turn on automatically If not the Entry Range should be increased slightly Do no...

Page 4: ...hts do not turn on after pressing the touchplate confirm that no other switches or equipment are interrupt ing or bypassing power to the relay transformer or load Disconnect the white wire from the transformer Wait 5 seconds and reconnect The relay should close on application of power and motion detection If the relay does not close check the wiring Momentarily short the relay control leads Red to...