Compares the local configuration file with the respective RPV311
configuration file.
Close the software with the "Exit" option.
2.2.2
Settings Menu
In the Settings menu, the user can:
Create, edit and remove Installations;
Create and remove Devices;
Transmission line configuration for TW fault location;
Create, edit and remove contacts for e-mail and fax sending;
Create, edit and remove Warnings to be sent.
Signing up RPVs to the RPV Manager:
The RPV Manager sorts the devices in the follow manner:
First, it is necessary to create what is called Installation, that can ben, for example,
the substation where de RPV is installed. Then the user has to register the RPV and
assign each of them to an installation by creating what is called Device.
Below mentioned is the procedure to create
Installations
and
Devices
.
1.1.1.1
CREATING INSTALLATIONS
The process to create a new Installation is:
1.
Click <S
ETTINGS
> menu and then click <I
NSTALLATIONS
>;
2.
Click <N
EW
> to create. Type the Installation's name and description and then
press <O
K
>.
The user can view the list of registered substations and add, edit, or remove a
substation. Substations can only be removed without any equipment being
associated.
1.1.1.2
CREATING DEVICES
The user can view the list of registered equipment, add, edit, or remove some
equipment. Equipment can only be removed when there is no transmission line
associated and if the Auto Polling is disabled. bellow
The process to create a new device is:
Click <S
ETTINGS
> menu and then click <D
EVICES
>;
Click <N
EW
> to create.
At <H
OST
>, type equipment's IP address;
Choose device installation in the Installation list;
Click at <Get Info> and then press <Ok>.
Generally, User name and Password are not required to download DFR registers. If
required for the application, then type Users name and password for administrator
user of the equipment (Alstom's default, user name is
admin
and password is
1234
).
The figure below shows the Device configuration window.
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...