RT411
Chapter 8
–
Technical Specification
32
RT411
Product safety protection
IP20 (due to live connection on the
terminal block)
7
Type Test
Table 10: EMC tests were performed according to IEC 60255-26 referring to the
following standards
IEC 61000-4-2:2008
6 kV contact / 8 kV air
IEC 61000-4-3:2006
10 V/m
IEC 61000-4-4:2012
2 kV @ 5 kHz
IEC 61000-4-5:2005
Differential mode: 1 kV
Common mode: 2 kV
IEC 61000-4-6:2008
10 V
IEC 61000-4-8:2009
30 A/m continuous
300 A/m @ 1 s
IEC 61000-4-11:2004
IEC 61000-4-29:2000
•
A.C. and D.C. voltage dips
Test level: 0% residual voltage
Duration time
A.C.: 1 cycle
D.C.: 16,6 ms
•
Test level: 40% residual voltage
Duration time
A.C.: 12 cycles
D.C.: 200ms
•
Test level: 70% residual voltage
Duration time
A.C.: 30 cycles
D.C.:500 ms
•
A.C. and D.C. voltage interruptions