background image

3

5B.  ATTACH WIRING USING A SUB-

BASE AND CHASEWAY

1.

  Remove the rectangular knockout at the bottom of the 

junction box. Remove the rectangular knockout at the 
right end of the sub-base.

2.  Wiring is placed between the two halves of the 

chaseway. Observe the orientation of the chaseway.

5B.  ATTACH WIRING USING A 

SUB-BASE AND CHASEWAY 
(continued)

3.

  Align the screw holes and secure the halves together 

using two type A screws.

Slide the upper end of chaseway with wiring protruding 
into rectangular knockout opening in the junction box. Be 
sure chaseway “ears” are on the inside of the box. Drive 
one type A screw through the junction box bottom into the 
chaseway “ear” hole. Insert lower end of chaseway into 
rectangular hole in sub-base and slide to right into the 
rectangular knockout making sure chaseway “ears” are 
inside the sub-base. Route wire toward the center of the 
sub-base. Drive one type A screw through the sub-base 
slotted hole into chaseway “ear” hole.

6. INSTALL JUNCTION BOX COVER

1.

  Make all wire connections by using appropriate NEC 

and UL listed electrical connectors and techniques.

2.

  For 20A and 30A power supply kits, plug in the 

personality jumper for heater selection.

3.

  Carefully tuck all wires and connections back 

inside the junction box. Be sure there are no loose 
connections or stray uninsulated wires exposed.

4.

  Place the junction box cover in place. Replace the 

two screws removed earlier and tighten securely.

5.

 Replace the Zoneline front cabinet.

5A.  ATTACH WIRING USING A FLEX 

CABLE

1.  

Use the round hole at the bottom of the junction box 
to attach flex cable coming from the branch circuit. 
Attach the conduit using proper conduit connector and 
bring wires into the junction box. Leave 6” of wire free 
at the end of the flex cable to allow connections to be 
made.

2.  

If a fuse and fuseholder are to be used, the 
knockout at the top of the box is for mounting a  
Buss Fuseholder. Be sure the fuse and fuseholder  
are of the same rating as the branch circuit. 
Leadwires at the fuse can be either soldered in place 
or attached using UL-listed 1/4” female (receptacle) 
crimp connectors.

ZONELINE SERIES – DIRECT ELECTRICAL CONNECTION

Installation Instructions

Knockout

Sub-base

Flex Cable

Direct Connect
Kit

Wiring

Chaseway

 cover

Chaseway

Direct Connect Kit

Junction Box

Summary of Contents for RAK315D

Page 1: ...Z9V series GE Zoneline units GE Zoneline AZ45 and AZ65 series units must be installed with a junction box RAK4002D purchased separately RAK515D RAK520D and RAK530D kits These kits are for use with 265V AZ45 AZ65 AZ95 and AZ9V series GE Zoneline Units FOR 230 208 VOLT DIRECT CONNECT APPLICATIONS ONLY IMPORTANT Some local electrical codes and customer requirements require PTAC units to be direct con...

Page 2: ...ew holding it to the assembly 3 INSTALL JUNCTION BOX 230 208V units Install the junction box by engaging the left tabs of the junction box with the slots on the control housing align the screw hole at the top and drive the screw until secure It is the responsibility of the installer to ensure the connection of components is done in accordance with the NEC local codes ordinances and regulations Dir...

Page 3: ...C and UL listed electrical connectors and techniques 2 For 20A and 30A power supply kits plug in the personality jumper for heater selection 3 Carefully tuck all wires and connections back inside the junction box Be sure there are no loose connections or stray uninsulated wires exposed 4 Place the junction box cover in place Replace the two screws removed earlier and tighten securely 5 Replace the...

Page 4: ...in receptacle in the junction box 6 Replace the junction box cover by replacing the three screws removed earlier NOTICE Wire junction box to match figure above Building supply wires and supply cord wires must both be secured with zip tie and oriented vertically Installation Instructions 1 REMOVE JUNCTION BOX COVER Remove the junction box cover by removing the three screws holding it to the assembl...

Page 5: ...NS À CONNEXION DIRECTES DE 265 VOLTS UNIQUEMENT IMPORTANT La connexion d un produit de 265 VCA à un circuit de dérivation DOIT être réalisée conformément avec le Code national de l électricité Le branchement de cet appareil à une prise exposée montée sur le bâtiment n est pas permis par le code Ces modèles doivent être installés en utilisant l ensemble de bloc d alimentation approprié pour l inten...

Page 6: ...ans le haut et vissez la vis 9RWUH LQVWDOODWHXU D OD UHVSRQVDELOLWp GH V DVVXUHU TXH OHV FRQQH LRQV GHV FRPSRVDQWV VRQW HႇHFWXpHV HQ FRQIRUPLWp DYHF OH FRGH national de l électricité et les codes et règlements locaux La connexion directe à un câblage de circuit de dérivation à l intérieur de la boîte de jonction doit être réalisée selon les indications ci dessous Calibres de câble recommandés pour...

Page 7: ...les en utilisant les connecteurs et les techniques homologués NEC et UL appropriés 2 Pour les ensembles d alimentation électrique 20A et 30A branchez le cavalier Personality afin de sélectionner l élément chauffant 3 Réinsérez délicatement tous les fils et raccords dans la boîte de jonction Assurez vous qu il n y a aucune connexion desserrée ou fil non isolé exposé et épars 4 Placez le couvercle d...

Page 8: ... à 4 voies dans la boîte de jonction 6 Replacez le couvercle de la boîte de jonction et réinstallez les trois vis retirées plus tôt AVIS La connexion des fils doit correspondre à l illustration ci dessus Les câbles d alimentation électrique du bâtiment et les fils du cordon d alimentation doivent tous être orientés verticalement et attachés avec une attache de câble 1 RETRAIT DU COUVERCLE DE LA BO...