FOR 7500 SERIES MODELS ONLY

7.

Make all wire connections by using appropriate UL-listed electrical
connectors and techniques.

8.

Select the applicable wiring situation and follow the instructions accordingly:

• 1

-Phase 220-240 VAC

When connecting the Zoneline to a single-phase circuit for 
230V applications:

Connect the white and black leads of the Zoneline power supply kit to the branch
circuit L1 and L2 leads. (The white lead of the power supply kit should be
identified by the installer using electrical tape with some color other than green or
white.) Connect the green lead of the power supply kit to the power supply and
branch circuit ground.

3-Phase 208 VAC

When connecting the Zoneline to a three-phase circuit for 
208V applications:

Connect the white and black leads of the Zoneline power supply kit to the branch
circuit L1 and L2 leads. (The white lead of the power supply kit should be
identified by the installer using electrical tape with some color other than green or
white.) Connect the green lead of the power supply kit to the power supply and
branch circuit ground.

3-Phase 208 VAC with “Crazy Leg”

When connecting the Zoneline to a three-phase circuit with “Crazy 
Leg” for 208V applications: 

Connect the white and black leads of the Zoneline power supply kit to the branch
circuit Neutral and L1 leads. (The white lead of the power supply kit should be
connected to neutral.) Connect the green lead of the power supply kit to the
power supply and branch circuit ground.

9.

Be sure that all wire leads are inside the junction box and not pinched
between the box and the unit. The green insulated ground wire from the
Zoneline 

MUST

be connected to the branch circuit ground wire

.

10.

Plug the 9-pin connector into the 9-pin receptacle in the junction box. 

11.

Replace the junction box cover by replacing the two screws removed
earlier.

12.

Replace the case front panel by replacing the four front screws and 
the two top screws. Replace the filter.

FOR 230/208 VOLT DIRECT CONNECT APPLICATIONS ONLY

4

Pub No. 31-60916     05-02 JR

Conduit

Make wire lead
connections

Printed in the United States

Summary of Contents for RAK3152

Page 1: ...r Note to Consumer Keep these instructions with your Owner s Manual for future reference TOOLS NEEDED 1 4 Nut driver Phillips screwdriver Wire cutter For direct connect applications only This kit is for use with 230 208 volt 5200 5500 and 7500 Series GE Zoneline units only IMPORTANT NOTES This unit must be properly grounded The electrical rating marked on the previously installed Zoneline and powe...

Page 2: ...e Zoneline operation 2 FOR 230 208 VOLT POWER CORD CONNECTIONS ONLY FOR 7500 SERIES MODELS ONLY 1 Remove the front panel by removing the filter taking out the four front screws the upper two screws from the top of the panel and the shipping screws on each side if present Discard the two side shipping screws if present 2 Remove the junction box cover and the junction box and discard 3 Connect the p...

Page 3: ...are engaged 10 Dress the wiring inside the junction box and attach the cover plate with screws A and C 11 Reinstall the room cabinet front FOR 230 208 VOLT DIRECT CONNECT APPLICATIONS ONLY 3 3 4 3 Connector 6 Conduit 9 pin connector Unit 9 pin receptacle C A C A B C A C A FOR 7500 SERIES MODELS ONLY 1 Measure 7 down the cord from where it emerges from the back of the yellow 9 pin connector and cut...

Page 4: ... with some color other than green or white Connect the green lead of the power supply kit to the power supply and branch circuit ground 3 Phase 208 VAC with Crazy Leg When connecting the Zoneline to a three phase circuit with Crazy Leg for 208V applications Connect the white and black leads of the Zoneline power supply kit to the branch circuit Neutral and L1 leads The white lead of the power supp...

Reviews: