11
4. Temperature Differential—Stage 3 (1–9°F) (.5-4.5°C)
Set the number of degrees between when stage 2 turns on
and stage 3 turns on
- Press the
<
or
>
button to set differential
value.
- Press the
FAN
(right) button to advance to the next screen.
-
Note:
Default factory setting is 1°F/.5ºC.
5. System -
Select appropriate cooling/heating system based on
model selection
- HP b2
: two stage cooling / two stage (B type)
heat pump with a backup 3rd stage of resistance
heat.
Use for AZ9V models.
- HP b1
: single stage cooling / single stage (B type) heat pump
with a backup 2nd stage of resistance heat.
Use for AZ95H and AZ65H models.
- ELC
: single stage cooling / single stage resistance heating.
Use for AZ95E and AZ45E Models.
- Press the
<
or
>
button to change selection.
- Press the
FAN (right)
button to advance to the next screen.
-
Note:
Default factory setting is HP b2.
6. Minimum Cool Setpoint (60, 64, 66, 68, 70, 72, 74, 76°F)
(15, 17, 19, 20, 21, 22, 23, 24°C)
Adjust to control the minimum Cool set
temperature allowed.
- Press the
<
or
>
button to select.
- Press the
FAN
(right) button to advance to the
next screen.
Note:
Default factory setting is 60°F/15°C.
CONFIGURATION MODE
:
HEAT