10
CONFIGURATION MODE
The configuration mode is used to set the RAK150VF2 to match
the heating/cooling system. The default setting of this thermostat
is for 2-stage cooling with a 3-stage heat pump system. For
an alternate configuration, see #7 in the
Configuration Mode
Settings
below.
To configure the RAK150VF2, perform the following steps:
1.
Ensure thermostat is in
OFF
mode.
2.
Remove the thermostat’s front cover.
3.
To enter the configuration mode, hold
CONFIG
for ~ 2 seconds.
4.
Once in the configuration mode, press the
<
or
>
button to
change settings within each screen.
-
Press the
FAN
(right)
button to advance to the next screen.
- Press the
MODE
(left)
button to return to the previous screen.
NOTE:
Hold
CONFIG
button for ~2 seconds to save changes
and exit configuration menu.
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
1.
Temperature Scale (°F or °C)—
Choose Fahrenheit or Celsius.
- Press the
<
or
>
button to select.
- Press the
FAN
(right) button to advance to the
next screen.
NOTE:
Default factory setting is
Fahrenheit
.
2.
Temperature Differential—Stage 1—(1–9°F) (.5-4.5°C)
Set the number of degrees between the “setpoint” temperature
and the “turn on” temperature for first stage.
- Press the
<
or
>
button to set differential
value.
- Press the
FAN
(right) button to advance to the next screen.
Note:
Default factory setting is 1ºF /.5ºC.
3. Temperature Differential—Stage 2 (1–9°F) (.5-4.5°C)
Set the number of degrees between when stage 1 turns on
and stage 2 turns on.
- Press the
<
or
>
button to set differential
value.
- Press the
FAN
(right) button to advance to the next screen.
-
Note:
Default factory setting is 1°F/.5°C.
:
: