Appendix B. Modbus Communication
46
PanaFlow™ XMT1000 User’s Manual
1A36
N/A
eAout4_
TestValue_Min
Minumum Analog Out 4
Test Value (Percent of
Span)
12
RO
4
(IEEE 32 bit)
1A38
N/A
eAout4_
BaseValue_Min
Minumum Analog Out 4
Base Value
1, 9, 14, 17,
20
RO
4
(IEEE 32 bit)
1A3A
N/A
eAout4_
FullValue_Min
Minumum Analog Out 4
Full Value
1, 9, 14, 17,
20
RO
4
(IEEE 32 bit)
MAIN Aout Min Int RO
1B00
MAIN Dout1 Real RW
2000
2000
Operator
eDout1_
PulseValue
Output_1 Pulse Value
17
RW
4
(IEEE 32 bit)
2002
Operator
eDout1_
PulseTime
Output_1 Pulse Time
10
RW
4
(IEEE 32 bit)
2004
Operator
eDout1_
FreqBaseValue
Output_1 Frequency Base
Value
1, 9, 14, 17,
20
RW
4
(IEEE 32 bit)
2006
Operator
eDout1_
FreqFullValue
Output_1 Frequency Full
Value
1, 9, 14, 17,
20
RW
4
(IEEE 32 bit)
2008
Operator
eDout1_
AlarmValue
Output_1 Alarm Value
1, 9, 14, 17,
20
RW
4
(IEEE 32 bit)
200A Operator
eDout1_
ControlValue
Output_1 Control Ouput
Value
17
RW
4
(IEEE 32 bit)
MAIN Dout1 Int RW
2100
2100
Operator
eDout1_
PulseTestValue
Output_1 Test Pulse Value
unitless
RW
4
INT32
2102
Operator
eDout1_
FreqFullFreq
Output_1 Frequency Full
Frequency
6
RW
4
INT32
2104
Operator
eDout1_
FreqTestValue
Output_1 Test Frequency
Value
6
RW
4
INT32
2106
Operator
eDout1_
FreqErrValue
Output_1 Frequency Error
Handling Value
6
RW
4
INT32
2180
2180
Operator eDout1_Type Output_1 type
unitless
RW
4
INT32
2182
Operator
eDout1_
PulseUnit
Output_1 Pulse Value Unit
Code
unitless
RW
4
INT32
2184
Operator
eDout1_
PulseErr
Output_1 Pulse Error
Handling
unitless
RW
4
INT32
2186
Operator
eDout1_
FreqAddress
Output_1 Frequency
Measument Register
Address
unitless
RW
4
INT32
2188
Operator
eDout1_
FreqErr
Output_1 Frequency Error
Handling
unitless
RW
4
INT32
218A Operator
eDout1_
FreqUnit
Output_1 Frequency Unit
code
unitless
RW
4
INT32
218C Operator
eDout1_
AlarmState
Output_1 Alarm State
unitless
RW
4
INT32
218E Operator
eDout1_
AlarmType
Output_1 Alarm Type
unitless
RW
4
INT32
Table 6: XMT1000 Modbus Register Map - Revision 4.19 (cont.)
Reg #
in Hex
Access
Level
Register ID Description
Units
RO/RW
Size in
Bytes
Format
Summary of Contents for PanaFlow XMT1000
Page 1: ...GE Oil Gas Flow 910 313 Rev A June 2017 PanaFlow XMT1000 User s Manual ...
Page 2: ......
Page 4: ...ii no content intended for this page ...
Page 8: ...Contents vi PanaFlow XMT1000 User s Manual no content intended for this page ...
Page 12: ...Preface x PanaFlow XMT1000 User s Manual no content intended for this page ...
Page 46: ...34 PanaFlow XMT1000 User s Manual no content intended for this page ...
Page 95: ......