Appendix A. Configuring Advanced User Parameters
254
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
A-2
Advanced User Parameter Definitions
Note:
The RX3i CPE305/CPE310 embedded Ethernet interface does not support all AUPs listed.
AUPs that can be used with CPE305/CPE310 are indicated by a footnote. Other
PACSystems Ethernet interfaces support the use of all AUPs listed in the following table.
System Memory Parameters (task b)
Default
Range
staudp
Remote command UDP port
18245 (4745H)
1 – 65535 (ffffH)
Only the gdata_port
and gXX_udp
parameters may
share the same UDP
port number. All other
UDP port number
parameters in the AUP
file must use unique
port numbers.
stpasswd
Station Manager password (only visible from MODIFY
prompt)
“system”
0 – 8 characters, case
sensitive, no spaces
Backplane Driver Parameters (task c)
Default
Range
crsp_tout
CPU response timeout. Amount of time to wait for the
CPU to respond to a request sent through the PLC
Driver.
60 seconds
10 – 3600 (E10H)
chct_comp
HCT compatibility option. (Rel 2.57 and later) Allows
Ethernet interface to ignore SRTP header errors
(typically generated by remote HCT devices) that
were not detected in previous Series 90 products.
0 = HCT compatibility disabled (= report all errors)
1 = HCT compatibility enabled (= ignore some errors)
0 (0H)
0, 1
cstorm
COMMREQ storm onset threshold. Establishes a
number of COMMREQs per second at or above which
the PLC application is considered to be sending
COMMREQs so rapidly that the Ethernet interface
cannot continue normal operation. Setting this
parameter to 0 disables COMMREQ storm error
detection.
500 (01F4H)
0 – 10,000 (2710H)
cnostorm
COMMREQ storm end threshold. Establishes the
number of COMMREQs per second at or below which
the COMMREQ storm condition (see above) is
considered to have ended. If the
cstorm
parameter is
not set to 0, this parameter should always be less
than
cstorm
. If
cstorm
is set to 0, this parameter is
ignored.
100 (0064H)
0 – 10,000 (2710H)
RDS Parameters (task d)
None
None
26
Supported by RX3i CPE305 and CPE310 models.
Summary of Contents for PACSystems RX7i
Page 45: ......
Page 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Page 81: ......
Page 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Page 147: ......
Page 211: ......
Page 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Page 263: ......