Chapter 3. CPU Configuration
136
PACSystems* RX7i, RX3i and RSTi-EP CPU Reference Manual
GFK-2222AD
Connecting to RSTi-EP CPE100/CPE115
Embedded Ethernet when IP Addresses
are not known
The default IP address (192.168.0.100) of CPE100/CPE115 can be
restored by powering up the module with the pushbutton pressed
and waiting until the OK LED flashes twice.
Note:
CPE100/CPE115.
Caution:
This procedure also erases the stored hardware
configuration, logic and contents of the backup RAM.