RX3i Ethernet Interface Module IC695ETM001-HW IPI 

GFK-2332Y 

August 2017 

 

 

Restrictions and Open Issues 

Subject 

Description 

COMMREQ Status Word value 

of 0x54A0 occasionally 

returned for EGD commands 

Occasionally a COMMREQ Status Word value of 0x54A0 is returned after 

COMMREQs for Ethernet Global Data commands when the previously-

transferred command has experienced retries in the network.  Executing 

the COMMREQ again results in successful transfer of the command. 

Modbus/TCP channel aborted 

during power-cycle 

After powering up an RX3i running Modbus/TCP client channels, the 

establish connection occasionally fails because the server rejects the 

"open" request from the client.  The connection will then succeed if the 

application retries the open when it sees a 0x9690 or 0xAA90 response to 

an open request or to the first write request. 

Controller response timeout 

errors (8/08) in Ethernet 

exception log under extremely 

heavy SRTP traffic 

Under extremely heavy SRTP traffic conditions, the Ethernet Interface may 

log an event in the Ethernet exception log (Event 8, Entry 2 = 08H) 

indicating an overload condition. This error terminates the SRTP 

connection.  If this event appears, either the traffic load should be 

reduced, or the application should use an alternate communications 

method to verify that critical data transfers were not lost due to the 

overload. 

SRTP channel transfers may 

take up to 20 seconds after 

power cycle 

When SRTP communications are interrupted by a power cycle, the 

Ethernet interface may require up to 20 seconds to reestablish TCP 

connection used for SRTP communications. 

"rmdir" Station Manager 

command does not work for 

multi-level directory path 

The "rmdir" Station Manager command does not operate properly with a 

multi-level directory path. Instead, first change to the parent directory, 

then delete the target directory without specifying a path. For example, 

the "rmdir dir1/dir2" results in "RMDIR Failed, dir1/dir2 does not exist". 

Instead, first do "cd dir1" and then "rmdir dir2". 

Intermittent Ethernet log event 

8H/15H after power cycle 

When starting after a power cycle, the Ethernet Interface may 

intermittently log an exception (entry 8H, Entry 2 = 15H, Entry 3 = 0000H, 

Entry 4 = 00aaH). This exception is benign and may be ignored. 

Intermittent Modbus/TCP 

Server log events when using 

"killms" Station Manager 

command 

When using the "killms" Station Manager command to manually terminate 

an active Modbus/TCP server connection, the following Modbus/TCP errors 

may occur in the Ethernet exception log: Event 2fH, Entry 2 = 209H, 212H, 

21bH, or 221H.  These errors may be ignored. 

Module intermittently 

unresponsive after reset 

Intermittently, when the module is restarted by using the pushbutton or 

Station Manager command, the module will blink its OK LED for 5 

minutes before completing the restart.  After the restart is complete the 

module fails to communicate with the CPU module.  The remedy is to 

power-cycle the PLC. 

A890 Commreq status after 

multiple Modbus open 

command attempts 

When using a Commreq to open a Modbus/TCP Channel to a remote 

server, if the initial Commreq returned an AA90 status, then future Open 

Commands may return A890 status. This indicates that local networking 

resources have been consumed and are not available for further 

connection attempts.  If this occurs, the application must wait at least 

60 seconds before making the next connection attempt.  This will allow 

networking resources to be released and made available for the next 

Modbus Open Command. 

Modbus/TCP request packets 

The Modbus/TCP server expects to receive each Modbus/TCP request in 

a separate TCP packet.  If multiple requests are sent in a single packet, 

the server may or may not send a response to each request.  If 

responses are sent to the client, they will be sent in separate TCP 

packets. 

Summary of Contents for PACSystems RX3i IC695ETM001-JW

Page 1: ... data exchange using Ethernet Global Data EGD EGD Commands to read and write controller and EGD exchange memory over the network TCP IP communication services using SRTP Support for SRTP Channels Modbus TCP Server and Modbus TCP Client Built in Station Manager for on line supervisory access to the Ethernet Interface Dedicated Station Manager port Two auto sensing 10Base T 100Base TX RJ 45 shielded...

Page 2: ...ion Manager Port RS 232 DCE 1200 115 200 bps Refer to the PACSystems RX3i System Manual GFK 2314 for product standards and general specifications Ethernet Interface Status Bits Note Unless LAN Interface OK Status Bit 16 is set the other status bits are invalid LAN Interface Status Bits 1 Port 1A full duplex 2 Port 1A 100Mbps 3 Port 1B full duplex 4 Port 1B 100 Mbps 5 Network Time Locked 6 Redundan...

Page 3: ... ETHERNET OK LAN OK LOG EMPTY Blink error code Off Off Hardware failure See chapter 11 for blink code definitions ETHERNET OK LAN OK LOG EMPTY Slow Blink Slow Blink Slow Blink All LEDs blink in unison pattern same while awaiting or performing load Firmware Update Field Wiring Station Manager RS 232 Port Pin Assignment Pin No Signal Direction Description 1 DCD IN Data Carrier Detect 2 TX OUT Transm...

Page 4: ...e enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This equates to a NEMA UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a pollution degree 2 environment For details about installing RX3i rack systems refer to GFK 2314 If you need technical help contact Technical Support For phone numbers and email addresses see the back cover of ...

Page 5: ...with all RX3i CPU models 1 RX3i rack power may be off or on hot insertion 2 Holding the module firmly align the module with the correct slot and connector then swing the module down until the module s connector engages the backplane s backplane connector Visually inspect the module to be sure it is properly seated 3 Insert the two provided M3x5mm machine screws through the module s bottom bracket ...

Page 6: ... IC693CMM321 is not supported by the RX3i and should not be placed in an RX3i rack Series 90 30 CPUs with embedded LAN Interface IC693CPU364 and IC693CPU374 like any Series 90 30 CPU should not be placed in an RX3i rack Modbus TCP support Release 3 60 of the PACSystems Ethernet Interface adds Modbus TCP Client Channels capability It supports Modbus Conformance Class 0 function codes 3 and 16 Confo...

Page 7: ...requiring a power cycle if it was subjected to heavy network storm traffic Reference GE Security Advisory is GE15 09 titled Network Storm Denial of Service In addition to the enhancement there were issues resolved Please refer to the Problems Resolved by This Release section above for more details IC695ETM001 HU 6 31 Nov 2015 Firmware release 6 31 IC695ETM001 HU provides a Field Upgrade Kit to add...

Page 8: ...change to the module s firmware or functionality IC695ETM001 ES 6 21 Jan 2014 Ethernet Firmware version fixes an issue with calculating DST correction in the European Union when SNTP is enabled IC695ETM001 ER 6 20 Jul 2013 Adds support in SNTP for local time zones and daylight savings time and resolves the field issues described on page 7 IC695ETM001 EP 6 14 Jul 2012 Resolves an issue with a spuri...

Page 9: ...e connections SRTP connections remain open after IP address changed The Ethernet Interface does not terminate all open SRTP connections before changing its IP address If the local IP address has changed any existing open TCP connections are unable to normally terminate This can leave SRTP connections open until their underlying TCP connections time out If quicker recovery of the SRTP connection is...

Page 10: ...ult can be safely ignored Unexpected EGD COMMREQ status EGD Commands may return COMMREQ Status 9590H internal error instead of the expected B190H Can t locate remote node when unable to locate a remote device on the network Very heavy EGD production consumption at server may cause EGD command timeouts Very heavy EGD production and or consumption at a server device may cause EGD command timeout err...

Page 11: ...ference memory sizes at the appropriate PLC Do not operate with CPU in incorrect slot The operation of the Ethernet interface is disrupted if the RX3i CPU is placed in a slot other than the one in which it is configured Various Ethernet exception log events may occur such as Entry 2 Entry 2 30 or 35 or 39 or 1e or 1f or Entry 8 Entry 2 b No CPU fault logged when Ethernet interface in fatal blink c...

Page 12: ... the parent directory then delete the target directory without specifying a path For example the rmdir dir1 dir2 results in RMDIR Failed dir1 dir2 does not exist Instead first do cd dir1 and then rmdir dir2 Intermittent Ethernet log event 8H 15H after power cycle When starting after a power cycle the Ethernet Interface may intermittently log an exception entry 8H Entry 2 15H Entry 3 0000H Entry 4 ...

Page 13: ... is disabled until the station manager password is changed to other than the default password The station manager password can be changed using an AUP file Refer to Appendix A Configuring Advanced User Parameters in TCP IP Ethernet Communications for PACSystems User s Manual GFK 2224K Changing the default Station Manager password is strongly recommended GE Intelligent Platforms strongly recommends...

Page 14: ...ess from a BOOTP server device on the network LAN must be tree not ring The two Ethernet network ports on the PACSystems RX3i Ethernet Interface must not be connected directly or indirectly to the same network device The hub or switch connections in an Ethernet network must form a tree and not a ring otherwise duplication of packets and network overload may result In this situation the RX3i Ethern...

Page 15: ...tain the underlying network and STRP connection Examples are establishing the TCP connection for a new channel establishing communication with the remote device and TCP retransmissions during Channel operations If the time needed for TCP connection establishment or maintenance exceeds the user specified channel application timeout values an application timeout will occur Channel application timeou...

Page 16: ...ucts and the Series 90 30 CPU364 EGD timestamps are taken from the Ethernet interface and do reflect CHTIME modifications ENIU Stale Data During Run Mode Store of EGD In a large PPS system running 20 ENIUs when a Run mode Store is performed that deletes the EGD exchanges for 10 of the ENIUs the other ENIUs will see the status on their exchanges indicate consumption timeouts during the RMS At the c...

Reviews: