6-30
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT INFORMATION
CHAPTER 6: ACTUAL VALUES
6
There is an identical menu for each of the breakers.
The
BKR 1 ACC ARCING AMP
values are in units of kA
2
-cycles. See the
COMMANDS
CLEAR RECORDS
menu for clearing
breaker arcing current records.
The
BREAKER OPERATING TIME
is defined as the slowest operating time of breaker poles that were initiated to open.
All of the values are stored in non-volatile memory and retained with power cycling.
6.6 Product information
6.6.1 Model information
ACTUAL VALUES
PRODUCT INFO
MODEL INFORMATION
The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.
The rear panel on the device contains similar information.
ETHERNET MAC ADDRESS
— UR devices with firmware 7.0x and above have three Ethernet ports that can be used on three
networks. The MAC address displays for port 1. The MAC address for port 2 is one higher. The MAC address for port 3 is one
higher than port 2. In redundant mode, the MAC addresses for ports 2 and 3 are the same as port 2.
BKR 1 AMP MAX
φ
B:
0.00 kA
BKR 1 AMP MAX
φ
C:
0.00 kA
MODEL INFORMATION
ORDER CODE LINE 1:
N60-A00-AAA-A0A-A0A-
Range: standard GE order code format
ORDER CODE LINE 2:
A0A-A0A-A0A
Range: up to 20 alphanumeric characters
ORDER CODE LINE 3:
Range: up to 20 alphanumeric characters
ORDER CODE LINE 4:
Range: up to 20 alphanumeric characters
SERIAL NUMBER:
Range: standard GE serial number format
ETHERNET MAC ADDRESS
000000000000
Range: standard Ethernet MAC address format
MANUFACTURING DATE:
Range: YYYY/MM/DD HH:MM:SS
OPERATING TIME:
0:00:00
Range: operating time in HH:MM:SS
PMU FEATURE ACTIVE:
No
Range: Yes, No
CT/ VT ADVANCED DIAG
ACTIVE: No
Range: Yes, No
LAST SETTING CHANGE:
1970/01/01 23:11:19
Range: YYYY/MM/DD HH:MM:SS