GEK-113000T
F650 Digital Bay Controller
6-17
6 COMMISSIONING
6.12 DIRECTIONAL ELEMENTS (67P, 67N, 67G, 67SG)
6
6.12.4 67SG ELEMENT
Activate only protection elements 50SG and 67SG and set the relay as follows:
Configure one of the outputs to be activated only by unit 50SG.
Apply the following tests:
67SG SETTINGS
50SG SETTINGS
Function
ENABLED
Function
ENABLED
MTA
-45 Deg
Input
PHASOR (DFT)
Direction
FORWARD
Pickup Level
0.50 A
Polarization
VO
Trip Delay
0.30
Block Logic
PERMISSION
Reset Delay
0.00
Pol V Threshold
10 V
ELEMENTS
PHASE UNDER TEST
POLARIZATION PHASE
ELEMENT TRIP
CHANNEL MAGNITUDE
CHANNEL
MAGNITUDE
MOD
ARG
MOD
ARG
50SG/67SG
ISG
2 A
0º
VI
60 V
0º
NO
60 V
180º
YES
VII
0 V
0º
VIII
0 V
0º
Summary of Contents for Multilin GEK-113000T
Page 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Page 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Page 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Page 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Page 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...