GEK-113000T
F650 Digital Bay Controller
6-3
6 COMMISSIONING
6.3 ISOLATION TESTS
6
6.3ISOLATION TESTS
During all tests, the screw located on the rear of the relay must be grounded.
For verifying isolation, independent groups will be created, and voltage will be applied as follows:
2200 RMS volts will be applied
progressively
among all terminals in a group, short-circuited between them and the
case, during one second.
2200 RMS volts will be applied
progressively
between groups, during one second.
WARNING:
No communication circuit shall be tested for isolation.
Groups to be created will depend on the type of modules included in F650, selectable according to the model.
The following table shows the different groups depending on the module type:
SOURCE 1:
G1
: H10, H18
G2
: H13, H14, H15
SOURCE 2:
G1
: H1, H9
G2
: H4, H5, H6
MAGNETIC MODULE.
G1
: A5..A12
G2
: B1..B12
I/O F1 (MIXED)
G1
(Inp. 1): F1..9
G2
(Inp. 2): F10..18
G3
(Out.): F19..36
I/O F2 (SUPERVISION)
G1
(Spv 1): F1..4
G2
(Inp. 1): F5..9
G3
(Inp. 2): F10..14
G4
(Spv 2): F15..18
G5
(Out.): F19..30
G6
(Out.): F31.36
I/O G1 (MIXED)
G1
(Inp. 1): G1..9
G2
(Inp. 2): G10..18
G3
(Out.): G19..36
I/O G4 (32DI)
G1
(Inp. 1): G1..9
G2
(Inp. 2): G10..18
G3
(Inp. 3): G19..28
G4
(Inp. 3): G29..36
I/O G4 (ANALOG)
G1
(Inp. 1): G1..9
G2
(Inp. 2): G10..18
Summary of Contents for Multilin GEK-113000T
Page 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Page 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Page 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Page 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Page 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...