6-26
G60 Generator Protection System
GE Multilin
6.3 METERING
6 ACTUAL VALUES
6
6.3.16 PHASOR MEASUREMENT UNIT
PATH: ACTUAL VALUES
METERING
PHASOR MEASUREMENT UNIT
PMU 1
The above actual values are displayed without the corresponding time stamp as they become available per the recording
rate setting. Also, the recording post-filtering setting is applied to these values.
PMU 1
PMU 1 VA:
0.0000 kV, 0.00°
Range: Va or Vab per VT bank connection
MESSAGE
PMU 1 VB:
0.0000 kV, 0.00°
Range: Va or Vab per VT bank connection
MESSAGE
PMU 1 VC:
0.0000 kV, 0.00°
Range: Va or Vab per VT bank connection
MESSAGE
PMU 1 VX:
0.0000 kV, 0.00°
MESSAGE
PMU 1 V1:
0.0000 kV, 0.00°
MESSAGE
PMU 1 V2:
0.0000 kV, 0.00°
MESSAGE
PMU 1 V0:
0.0000 kV, 0.00°
Range: Substituted with zero if delta-connected VTs.
MESSAGE
PMU 1 IA:
0.0000 kA, 0.00°
MESSAGE
PMU 1 IB:
0.0000 kA, 0.00°
MESSAGE
PMU 1 IC:
0.0000 kA, 0.00°
MESSAGE
PMU 1 IG:
0.0000 kA, 0.00°
MESSAGE
PMU 1 I1:
0.0000 kA, 0.00°
MESSAGE
PMU 1 I2:
0.0000 kA, 0.00°
MESSAGE
PMU 1 I0:
0.0000 kA, 0.00°
MESSAGE
PMU 1 FREQUENCY:
0.0000 Hz
MESSAGE
PMU 1 df/dt:
0.0000 Hz/s
MESSAGE
PMU 1 CONFIG CHANGE
COUNTER: 0
Range: 0 to 65535
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...