F485 COMMUNICATIONS CONVERTER – INSTRUCTION MANUAL

5

Configuration

The converter box is configured via two internal dip switch banks which are accessible by 
removing the converter box cover. Switches A1-A8 are used to set the baud rate for RS485 
communications and determine whether the converter is DTE (RS232 direct) or DCE (RS232 
modem). Switches B1-B6 are used to select the interface type. The designator for each 
switch is clearly marked on the printed circuit board. The tables shown provide a 
description of each switch within the switch banks.

Table 1: Switch A (baud rates)

Table 2: Switch A (DTE/DCE)

Table 3: Switch B (configuration)

Baud rates

Two-wire RS485 is half duplex and requires a means for switching between a receive or 
transmit state. The F485 converter uses the incoming data to control the direction and 
therefore requires no control signals from the master device (RS232 or fiber) to switch from 
transmit to receive mode after the last character has been transmitted. The baud rate 
switches control the length of time that the RS485 transmitter will remain in the transmit 
direction after the last character has been transmitted. The length of time is fixed at 3.5 
character times at the selected baud rate making it suitable for use with Modbus® RTU 
protocol. When converting RS232 to FIBER, these switches (A1-7) have no effect.

BAUD

A1

A2

A3

A4

A5

A6

A7

1200

ON

OFF

OFF

OFF

OFF

OFF

OFF

2400

OFF

ON

OFF

OFF

OFF

OFF

OFF

4800

OFF

OFF

ON

OFF

OFF

OFF

OFF

9600

OFF

OFF

OFF

ON

OFF

OFF

OFF

19200

OFF

OFF

OFF

OFF

ON

OFF

OFF

38400

OFF

OFF

OFF

OFF

OFF

ON

OFF

57600

OFF

OFF

OFF

OFF

OFF

OFF

ON

MODE

A8

DTE

OFF

DCE

ON

CONFIGURATION B1

B2

B3

B4

B5

B6

RS232 TO RS485

OFF

ON

OFF

ON

OFF

OFF

RS232 TO FIBER

OFF

OFF

OFF

OFF

ON

ON

RS485 TO FIBER

ON

OFF

ON

OFF

OFF

OFF

Summary of Contents for Multilin F485

Page 1: ...F485 Communications Converter Instruction Manual F485 Communications Converter Manual P N 1601 0073 A5 GE publication code GEK 119569A GE Grid Solutions 1601 0073 A5 LISTED ...

Page 2: ...without notice Part number 1601 0073 A5 September 2017 Revision history Release Dates Major Updates for A5 Major Updates for A4 Part No Revision Release Date 1601 0073 A3 1 0x April 2003 1601 0073 A4 1 0x July 2013 1601 0073 A5 1 0x September 2017 Page Changes Cover Manual revision from A4 to A5 Branding format and colors updated to GE Grid Solutions Bar code 10 year warranty UL logo added Page 1 ...

Page 3: ...849 UL Listed for the USA and Canada Contact information For product support contact the information and call center as follows GE Grid Solutions 650 Markland Street Markham Ontario Canada L6C 0M1 Worldwide telephone 1 905 927 7070 Europe Middle East Africa telephone 34 94 485 88 54 North America toll free 1 800 547 8629 Fax 1 905 927 5098 Worldwide e mail multilin tech ge com Europe e mail multil...

Page 4: ...2 F485 COMMUNICATIONS CONVERTER INSTRUCTION MANUAL Typical Configurations Figure 1 RS232 to RS485 connection 805753A3 CDR ...

Page 5: ...F485 COMMUNICATIONS CONVERTER INSTRUCTION MANUAL 3 Figure 2 RS232 to FIBER and FIBER to RS485 805754A3 CDR ...

Page 6: ...ect the supplied power adapter to this input if power is not supplied via the terminals The power adapter steps down 120 220 VAC to 9 VAC RS485 The RS485 terminals accept a standard shielded twisted pair such as Beldon 9841 and provide connections for a and a shield The RS485 terminals have a terminating network installed internally and therefore no external terminating network is required Observe...

Page 7: ...ng data to control the direction and therefore requires no control signals from the master device RS232 or fiber to switch from transmit to receive mode after the last character has been transmitted The baud rate switches control the length of time that the RS485 transmitter will remain in the transmit direction after the last character has been transmitted The length of time is fixed at 3 5 chara...

Page 8: ...The fiber optic transmitter and receiver used in the F485 converter utilize 820nm wavelength technology and are designed to operate with 50 125µm 62 5 125µm and 100 140µm fiber sizes using ST terminated cables The ST connections provide repeatable connections within 0 2 dB typically The transmitter receiver pair will typically work with fiber lengths up to 1km Ensure the dust covers are installed ...

Page 9: ...N CONNECTOR 8 8 5 6 6 6 Rx FIBER 9VAC 120 220 VAC POWER ADAPTER POWER JACK POWER SUPPLY 9VAC 9VDC 9VDC 5V POWER 5V ISOLATED RS485 CONVERTER TERMINATION AND LINE BIAS RS485 LED Rx SR489 IN SERVICE BREAKER OPEN R1 TRIP R2 AUXILIARY R3 AUXILIARY R4 AUXILIARY R5 ALARM R6 SERVICE SETPOINT ACCESS BREAKER CLOSED COMPUTER RS232 HOT STATOR MESSAGE VT FAILURE BREAKER FAILURE PROGRAM PORT SETPOINT 7 8 9 4 5 ...

Page 10: ...8 F485 COMMUNICATIONS CONVERTER INSTRUCTION MANUAL Dimensions Figure 5 Dimensions 805750A5 CDR ...

Reviews: