2–22
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
IEC 60870-5-103 SERIAL COMMUNICATION
CHAPTER 2: RS485 INTERFACE
This means that for each digital point 3 settings are required.
Example
:
The “Point Entry Digital Status” reuses the DNP Binary Input 43029, 43030, …
Measurands
Some analog points are supported by the 350 relay, with compatible information number
that have been identified in the device profile.
For the other measurands, it is possible to use the EnerVista SR3 Setup to select the desired
point and assign the Identification Type (3 or 9), Function Type <0..255>, and Information
Number <1..255>.
If the user selects Identification Type 3 (ASDU 3) only four measurands are available for
configuration, but if Identification Type 9 (ASDU 9) is selected, up to nine measurands can
be sent in the IEC103 slave answer. For each measurand, all metering values that the
350 supports, are available in order to be mapped. There are 3 possible configurable
ASDUS.
For example, eDataVab is the index in the Modbus Memory Map.
Settings
Digital Status
Information Number
Function Type
Point 1 Entry
Select entry from list
<0 – 255 >
<0 – 255 >
….
.…
Point 64 Entry
Select entry from list
<0 – 255 >
<0 – 255 >
Modbus Address
Description
Value
Format
43879
Point 1 Entry Digital Status
0x8242 (Undercurrent Trip)
FC134
44223
Point 1 Entry Function Type
160
F1
44224
Point 1 Entry Information Number
144
F1
Modbus Address
Description
Value
Format
44384
First ASDU Identification Type
3 or 9
F1
44385
First ASDU Function Type
<0 – 255 >
F1
44386
First ASDU Information Number
< 0 – 255 >
F1
44387
First ASDU Scan Timeout
< 0 – 1000> secs
F1
44388
First ASDU First Analog Entry
Vab
F1
44389
First ASDU First Analog Factor
1
F3
44390
First ASDU First Analog Offset
0
F1
44391
First ASDU Second Analog Entry
Ib
F1
44392
First ASDU Second Analog Factor
1
F3
44393
First ASDU Second Analog Offset
0
F1
...
...
...
...
44412
First ASDU Ninth Analog Entry
Ib
F1
44413
First ASDU Ninth Analog Factor
1
F3
...
...
...
...
44443
Second ASDU Ninth Analogue Entry
44444
Second ASDU Ninth Analogue Factor
44445
Second ASDU Ninth Analogue Offset
...
...
...
...