4–56
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
IEC 61850 LOGICAL NODES
CHAPTER 4: SR3 IEC61850 GOOSE
Table 4-26: RREC Autoreclosing
Logical Nodes for generic references (LN Group: G)
GGIO (Generic process I/O)
Table 4-27: GGIO1 to Remote Outputs (available only with Simplified Goose setting)
Table 4-28: GGIO2 to Contact Inputs/Outputs
RBRF class
Attribute Name
Attr. Type Explanation
M/O
Notes
RREC
Autoreclosing
Data
Common Logical Node Information
Mod
INC_0
Mode
M
Beh
INS_0
Behaviour
M
Health
INS_1
Health
M
NamPlt
LPL_1
Name plate
M
Status Information
Op
ACT_2
Operate
M
AutoRecSt
INS_3
AutoReclosing Status
M
GGIO class
Attribute Name
Attr. Type Explanation
M/O
Notes
GGIO
Generic process I/O
Data
Common Logical Node Information
Mod
INC_0
Mode
M
Beh
INS_0
Behaviour
M
Health
INS_1
Health
M
NamPlt
LPL_1
Name plate
M
Status information
Ind1
SPS_0
General Indication
( binary input )
O
Remote Output 1
Ind2
SPS_0
General Indication
( binary input )
O
Remote Output 2
..
..
..
..
..
Ind32
SPS_0
General Indication
( binary input )
O
Remote Output 32
GGIO class
Attribute Name
Attr. Type
Explanation
M/O
Notes
GGIO
Generic process I/O
Data
Common Logical Node Information
Mod
INC_0
Mode
M
Beh
INS_0
Behaviour
M
Health
INS_1
Health
M
NamPlt
LPL_1
Name plate
M
Status information
Ind1
SPS_0
General Indication
( binary input )
O
Contact Input 1