Masoneilan SVi1000 Bench Quick Start Manual 

=

|

 

7

© 2016 General Electric Company. All rights reserved.

7. Click 

Settings > Field Networks

,

 

click 

Add

 and Figure 4 appears. Select 

HART Modem

 and 

click 

OK

Figure 4 Add Field Network

8. Click 

OK

 again to add the 

HART Modem 

to 

Network View

 and Figure 5 appears.

Figure 5 HART Modem Configuration Tab

Summary of Contents for Masoneilan SVi 1000

Page 1: ...GE Oil Gas Masoneilan SVi 1000 Advanced Performance Digital Positioner Bench Quick Start Rev B Instruction Manual GE Data Classification Public ...

Page 2: ...S AND REGULATIONS APPLICABLE AT THE SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION OPERATION OR MAINTENANCE SHOULD FURTHER INFORMATION BE DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT...

Page 3: ...hen to run signatures and produce associated reports This procedure uses GE s ValVue 3 software ver 3 20 or later and the SVi1000 DTM ver 2 20 0 or later This procedure consists of the following major steps 1 Physical Setup on page 4 2 Software Install and Configuration on page 5 3 Perform Setup Wizard on page 10 4 Save Settings and Device Baseline on page 12 Changing the Application to Normal mod...

Page 4: ...lugged If it does not the VIATOR installation includes a utility called USB View for viewing USB connections For a serial connection you can check using Windows Device Manager 3 Prepare the HART hardware by a Plugging the HART Loop Power Calibrator power supply in and setting up the calibrator as per its manual ensuring the mode is correct to supply a 4 20 mA b Plugging the USB plug or serial conn...

Page 5: ...rights HART Communication DTM and install See Codewrights HART Communication DTM on page 15 for download site 3 Sign on to ValVue 3 with default values User name admin Password ValVue 3 For security purposes you are forced to change your password during the first use GE recommends registering your software immediately You are required to register after a 30 day trial period After the trial period ...

Page 6: ...Figure 2 appears Figure 2 DTM Library Management Before Update 5 Click Update and once the DTM Updates list refreshes select the HART Communications and the SVi1000 HART 5 or HART 7 Figure 3 DTM Library Management After Update 6 Click Add Sel and then click OK to close DTM Library Management dialog ...

Page 7: ...ric Company All rights reserved 7 Click Settings Field Networks click Add and Figure 4 appears Select HART Modem and click OK Figure 4 Add Field Network 8 Click OK again to add the HART Modem to Network View and Figure 5 appears Figure 5 HART Modem Configuration Tab ...

Page 8: ...lowing Selecting Network Rebuild Network or Selecting Find New Devices or Clicking Add New Device Figure 6 appears highlighting SVi1000 HART 5 or 7 and clicking OK Figure 6 Add New Device 11 Right click on the SVi1000 in the Project pane and click Connect 12 Click OK to the DTM evaluation period warning if it appears The SVi1000 DTM opens If device is connected or powered through DCS set Master to...

Page 9: ...ick Apply Disconnect and then reconnect Figure 8 Communication Tab 14 Click Upload All Parameters icon see red box in Figure 7 GE recommends registering your software GE recommends registering your software immediately You are required to register after a 30 day trial period After the trial period you won t be able to use the software until you complete the registration process that the software g...

Page 10: ...nge calibration confirm that the valve is isolated from the process This procedure exhausts and then fills the valve actuator to supply pressure and therefore strokes the valve over its full range Supply pressure MUST NOT exceed the actuator pressure rating marked on the actuator Positioner supply pressure MUST BE at least 5 psi higher than the upper spring range of the valve CAUTION Procedures e ...

Page 11: ...ab and ensure the mode is in Setup Figure 9 Full Wizard Tab 2 Set the Current Slot to either 0 for ATO or 8 for ATC 3 Click an item in the Procedure Name list or click Check All This procedure moves the valve Procedures e g Find Stops Auto Tune Step Test and Ramp Test should NOT be invoked if the ValVue sequencer is running ...

Page 12: ...e Settings and Device Baseline 1 Perform any needed diagnostic tests and run tests using the Full Wizard or the Diagnostics functionalities See the SVi1000 DTM online help for steps to configure and run diagnostic tests Save the results 2 After finishing with the control valve make sure all saved reports contain all necessary order information by a Right clicking the SVi1000 device in the Project ...

Page 13: ...g the Disconnect icon on the ValVue 3 toolbar c Clicking Network Exit to close the DTM If you have unsaved data click the Download Parameters to Device icon to save 3 Connect SVi1000 wires to next item on order Click Find New Devices Go to step 10 of 2 Software Install and Configuration on page 5 and repeat ...

Page 14: ... ge mcs com en download html make selections as shown Figure 11 and click Search Figure 11 Download Center Search for Valve 3 The results appear Figure 12 Figure 12 Search Results ValVue 3 Figure 13 Download Center Search for SVi1000 DTM 2 Scroll down to find the specific software program of choice SVi1000 DTM or ValVue 3 Click the blue link to download ...

Page 15: ... save the download file to your laptop PC Don t install from the website Codewrights HART Communication DTM You must download and install this DTM to use Masoneilan s HART based DTM Go to the link http www codewrights biz index php en downloads software and follow instructions to download and install the CW_CommDTM_HART Filling in this form registers the download It does not register the software ...

Page 16: ...8666 Fax 88 31 18 1641438 Skelmersdale Phone 44 1695 526 00 Fax 44 1695 526 01 FRANCE Courbevoie Phone 33 1 4904 9000 Fax 88 33 1 4904 9010 RUSSIA Veliky Novgorod Phone 7 8162 55 7898 Fax 88 7 8162 55 7921 UNITED STATES Massachusetts Phone 1 508 586 4600 Fax 88 1 508 427 8971 GERMANY Ratingen Phone 49 2102 108 0 Fax 88 49 2102 108 111 Moscow Phone 7 495 585 1276 Fax 88 7 495 585 1279 Corpus Christ...

Reviews: