CHAPTER 7: TESTING
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
7–11
7.3
Additional Functional Testing
7.3.1
Overload Curve Test
The 469 specification for overload curve timing accuracy is
±
100 ms or
±
2% of time to trip.
Pickup accuracy is as per the current inputs (
±
0.5% of 2
×
CT when the injected current is
less than 2
×
CT and
±
1% of 20
×
CT when the injected current is
≥
2
×
CT). Perform the
steps below to verify accuracy.
Alter the following settings:
S2 SYSTEM SETUP
CURRENT SENSING
PHASE CT PRIMARY:
“1000”
S2 SYSTEM SETUP
CURRENT SENSING
MOTOR FULL LOAD AMPS FLA:
“1000”
S5 THERMAL MODEL
THERMAL MODEL
SELECT CURVE STYLE:
“Standard”
S5 THERMAL MODEL
THERMAL MODEL
OVERLOAD PICKUP LEVEL:
“1.10”
S5 THERMAL MODEL
THERMAL MODEL
UNBALANCE BIAS K FACTOR:
“0”
S5 THERMAL MODEL
THERMAL MODEL
HOT/COLD SAFE STALL RATIO:
“1.00”
S5 THERMAL MODEL
THERMAL MODEL
ENABLE RTD BIASING:
“No”
S5 THERMAL MODEL
O/L CURVE SETUP
STANDARD OVERLOAD CURVE NUMBER:
“4”
Any trip must be reset prior to each test.
Short the emergency restart terminals momentarily immediately
prior to each overload curve test to ensure that the thermal capacity
used is zero.
Failure to do so will result in shorter trip times.
Inject the current of the proper amplitude to obtain the values as
shown.
Verify the trip times.
Motor load may be viewed in:
A2 METERING DATA
CURRENT METERING
.
Thermal capacity used and estimated time to trip may be viewed in
A1 STATUS
MOTOR STATUS
.
7.3.2
Power Measurement Test
The specification for reactive and apparent power is
±
1% of
×
2
×
CT
×
VT
×
VT full
scale at
I
avg
<
2
×
CT. Perform the steps below to verify accuracy.
AVERAGE
PHASE
CURRENT
DISPLAYED
PICKUP
LEVEL
EXPECTED
TIME TO
TRIP
TOLERANCE
RANGE
MEASURED
TIME TO
TRIP
1050 A
1.05
never
n/a
1200 A
1.20
795.44 sec.
779.53 to 811.35 sec.
1750 A
1.75
169.66 sec.
166.27 to 173.05 sec.
3000 A
3.00
43.73 sec.
42.86 to 44.60 sec.
6000 A
6.00
9.99 sec.
9.79 to 10.19 sec.
10000 A
10.00
5.55 sec.
5.44 to 5.66 sec.
3
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...