54
469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
COMMUNICATIONS GUIDE
183E
Reserved
...
...
184D
Reserved
184E
RTD #6 alarm temperature (in Fahrenheit)
34
482
1
°F
F1
266
184F
RTD #6 trip temperature (in Fahrenheit)
34
482
1
°F
F1
311
RTD #7
1850
RTD #7 application
0
4
1
--
F121
2
1851
RTD #7 alarm
0
2
1
--
F115
0
1852
RTD #7 alarm relays
0
6
1
--
F113
0
1853
RTD #7 alarm temperature
1
250
1
°C
F1
80
1854
RTD #7 alarm events
0
1
1
--
F103
0
1855
RTD #7 trip
0
2
1
--
F115
0
1856
RTD #7 trip voting
1
12
1
--
F122
7
1857
RTD #7 trip relays
0
3
1
--
F111
0
1858
RTD #7 trip temperature
1
250
1
°C
F1
90
1859
1st and 2nd characters of RTD #7 name
0
65535
1
--
F22
‘ ’
185A
3rd and 4th characters of RTD #7 name
0
65535
1
--
F22
‘ ’
185B
5th and 6th characters of RTD #7 name
0
65535
1
--
F22
‘ ’
185C
7th and 8th characters of RTD #7 name
0
65535
1
--
F22
‘ ’
185D
Reserved
185E
Reserved
...
...
186D
Reserved
186E
RTD #7 alarm temperature (in Fahrenheit)
34
482
1
°F
F1
176
186F
RTD #7 trip temperature (in Fahrenheit)
34
482
1
°F
F1
194
RTD #8
1870
RTD #8 application
0
4
1
--
F121
2
1871
RTD #8 alarm
0
2
1
--
F115
0
1872
RTD #8 alarm relays
0
6
1
--
F113
0
1873
RTD #8 alarm temperature
1
250
1
°C
F1
80
1874
RTD #8 alarm events
0
1
1
--
F103
0
1875
RTD #8 trip
0
2
1
--
F115
0
1876
RTD #8 trip voting
1
12
1
--
F122
8
1877
RTD #8 trip relays
0
3
1
--
F111
0
1878
RTD #8 trip temperature
1
250
1
°C
F1
90
1879
1st and 2nd characters of RTD #8 name
0
65535
1
--
F22
‘ ’
187A
3rd and 4th characters of RTD #8 name
0
65535
1
--
F22
‘ ’
187B
5th and 6th characters of RTD #8 name
0
65535
1
--
F22
‘ ’
187C
7th and 8th characters of RTD #8 name
0
65535
1
--
F22
‘ ’
187D
Reserved
187E
Reserved
...
...
188D
Reserved
188E
RTD #8 alarm temperature (in Fahrenheit)
34
482
1
°F
F1
176
Table 7: 469 MEMORY MAP (Sheet 36 of 90)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT