background image

8  |  GE Oil & Gas

© 2016 General Electric Company. All rights reserved.

4.3 Installation

4.3.1 Positioning

 

All 173-50 regulators must be installed with the actuator facing 

upwards and the diaphragm horizontal.

4.3.2

 Installation Diagrams

In most cases the flow crosses the regulator as shown by the 
arrow in Figures 9 and 10.

The installation diagrams are therefore as follows:

Figure 11

Example of installation layout for 173-50 single diaphragm 
regulators

Figure 12

Example of installation layout for 173-50 double diaphragm 
regulators

4.3.3 Isolation Valves and Filter/Pressure Gauges

Install an isolation valve upstream, downstream and on the 
sensing and discharge line connection piping, in order to service 
the regulator (if necessary) while the plant is pressurized. 

Install one filter or pressure gauge upstream from the regulator 
and another one on the sensing line connection (as shown in 
Figures 11 and 12) in order to calibrate the differential pressure 
and keep it constantly under control.

4.3.4 Contamination

 

Prior to installing the regulator in the piping, make sure the inside 
of the pipes are clean and free of any debris (machining cuttings, 
weld slag, etc.), especially the upstream section; blow down the 
piping if possible to eliminate any remaining dirt: small drops of 
weld slag may seriously damage the regulator.

4.3.5 Double Diaphragm Discharge Venting

In double diaphragm regulators, the chamber between the two 
diaphragms must be connected to piping to vent the discharge 
to a suitable place, safely and constantly at atmospheric 
pressure. This hole can be closed with a plug or pressure gauge 

with an electrical contact for the remote signaling that the 
diaphragm has broken, as long as the downstream plant is 
protected (as shown in Figure 12).

4.3.6 Safety Relief

If there is any chance that an overflow regulator failure could 
cause the pressure upstream from the reduction regulator to 
exceed the maximum admissible pressure for the installation, 
a safety relief valve must be installed upstream – without an 
isolation valve in between – in order to discharge the entire flow 
crossing the differential pressure regulator.

4.3.7 Pressure Drops

Because the regulated pressure sensing port is located inside 
the regulator, the pressure drops in the inter-connecting piping 
between the regulator and the point of use will affect the 
accuracy of the maintained set pressure. This pressure drop 
must be considered when calculating the size of the connection. 

4.3.8 Pressure Variation 

When it is essential to avoid pressure variations at the point 
of use, the regulators are fitted with an external sensing line 
connection that replaces the internal connection and is fitted 
to the lower flange of the actuator. This connection must be 
connected as near as possible to the point of use where the 
installation of a pressure gauge is also recommended.

4.4 Startup and Calibration

(Refer to Figures 9 and 10)

4.4.1 Pressure Difference

This operation is similar for both single diaphragm and double 
diaphragm regulators. The sensing line connection regulator and 
the upstream and downstream isolation valves must be closed. 
Slightly open the downstream valve and then the upstream 
valve together with the sensing line connection, making sure 
that the pressure difference read on the pressure gauges is 
correct. If necessary, to reduce the pressure difference, turn the 
adjustment screw (18) clockwise to increase differential pressure 
and counterclockwise to decrease. 

4.1.2 Calibration 

When the required value is reached, fully open all the valves. 
When the downstream system is working at full power, calibrate 
by adjusting the screw (18).

4.5 Maintenance

(Refer to Figures 9 and 10)

4.5.1 Maintenance Interval

The required maintenance interval will vary depending on 
application. The user must establish a suitable maintenance 
schedule depending on the operating conditions. Prior to 
disassembly, remove all system pressure from the regulator.

Before starting the above operation, make sure the recommended 
spare parts are available (See the parts listed in Figures 9 and 10).

Summary of Contents for Masoneilan 173 Series

Page 1: ...GE Oil Gas Masoneilan 173 Series Self Operating Pressure Regulators Instruction Manual GE Data Classification Public ...

Page 2: ...HE SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION OPERATION OR MAINTENANCE SHOULD FURTHER INFORMATION BE DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE CUS...

Page 3: ...d Handling 2 3 Installation and Assembly Instructions 173 Series Pressure Regulator 3 1 Cross Section Drawing 3 3 2 Installation 4 3 3 Start Up and Calibration 4 3 4 Maintenance 5 4 Installation and Assembly Instructions 173 50 Differential Pressure Regulator 4 1 Cross Section Drawing 173 50 Single Diaphragm 6 4 2 Cross Section Drawing 173 50 Double Diaphragm 7 4 3 Installation 8 4 4 Start Up and ...

Page 4: ...result in property damage Note Indicates important facts and conditions About this Manual The information in this manual is subject to change without prior notice The information contained in this manual in whole or part shall not be transcribed or copied without GE s written permission Please report any errors orquestions about the information in this manual to your local supplier Theseinstructio...

Page 5: ... All the regulator ends are fitted with covers to prevent dirt from entering Units can be placed on pallets if required Follow all instructions noted on the packaging Operators moving loads must take all necessary precautions to prevent accidents Storage Regulators must be kept in a dry place to protect them from atmospheric conditions They may only be removed from their crates or packing immediat...

Page 6: ... with part names and versions ATEX Construction Gr II Cat 2 Ref Part Name 1 Blindhead 2 Gasket Set 3 Body 4 Guide 5 Diaphragm Case 6 Ball 7 Diaphragm Plate Upper 8 Diaphragm 9 Protector optional 10 O Ring 11 Spring Case 12 Spring 13 Adjusting Screw 14 Lock Nut 15 Spring Button 16 Nut 17 Spring Guide 18 Screw 19 Nut 20 Diaphragm Plate Lower 21 Screw 22 Plug 23 Ring 24 Disc 25 Seat 26 Screw 27 Gaske...

Page 7: ... to decrease the pressure setting During regulator start up or operation do not touch any part of the regulator as this can conduct heat if the fluid used is at a high temperature 3 2 Installation 3 2 1 173 Series regulators must be installed with the actuator 2 facing upwards and the diaphragm perfectly horizontal as shown in Fig 6 In pressure reducing applications regulating very low down stream...

Page 8: ...his may damage important sliding parts 3 4 Maintenance 3 4 1 The required maintenance interval varies depending on application The user must establish a suitable interval based on the operating conditions Prior to disassembly remove all system pressure from the regulator Before starting the above operation make sure the recommend ed spare parts are available refer to the parts list indicated in Fi...

Page 9: ... a single diaphragm as shown in Figure 9 one of the controlled pressures acts under the diaphragm through an internal sensing line connection on the spring housing The plug is kept closed by the spring Ref Part Name 1 Blindhead 2 Gasket Set 3 Body 4 Guide 5 Diaphragm Case 6 Diaphragm Plate Upper 7 Diaphragm 8 O Ring 9 Spring Case 10 Spring 11 Nut 12 Screw 13 Gasket 14 Lock Nut 15 Packing Gland 16 ...

Page 10: ...nsing line connection and over the upper diaphragm through a sensing line nipple on the spring housing The plug is kept closed by the spring Figure 10 Ref Part Name 1 Blindhead 2 Gasket Set 3 Body 4 Guide 5 Diaphragm Case 6 Diaphragm Plate Upper 7 Diaphragm 8 O Ring 9 Spring Case 10 Spring 11 Nut 12 Screw 13 Gasket 14 Packing Gland 15 Lock Nut 16 Bearing 17 Spring Button 18 Adjusting Screw 19 Spri...

Page 11: ... pressure for the installation a safety relief valve must be installed upstream without an isolation valve in between in order to discharge the entire flow crossing the differential pressure regulator 4 3 7 Pressure Drops Because the regulated pressure sensing port is located inside the regulator the pressure drops in the inter connecting piping between the regulator and the point of use will affe...

Page 12: ... to be restored by lapping using a metal disc and abrasive paste The diaphragm should be replaced if it shows any damage The same applies to the Teflon diaphragm protector if included Gaskets should not be reused If preferred the regulator may be returned to an authorized GE repair center to be reconditioned 4 5 4 Reassembly Carry out the disassembly operations in reverse order Push the stem of th...

Page 13: ...10 GE Oil Gas 2016 General Electric Company All rights reserved ...

Page 14: ...Masoneilan 173 Series Pressure Regulator Instruction Manual 11 2016 General Electric Company All rights reserved ...

Page 15: ...12 GE Oil Gas 2016 General Electric Company All rights reserved ...

Page 16: ...of their respective owners 2014 General Electric Company All rights reserved Visit our web site www fr eps com E P S FRANCE 24 bis rue de Picpus 75012 PARIS Tel 33 0 762 682 291 Tel 33 0 650 590 965 ventes fr eps com E P S CAMEROON Immeuble Carré d Or Rue Soppo Priso Côté Chococho Bonapriso DOUALA Tel 237 6 52 12 70 95 Tel 33 0 782 006 276 ventes fr eps com ...

Reviews: