CHAPTER 4: INTERFACES
FLEXLOGIC DESIGN USING ENGINEER
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
4-71
4
Warnings
When using the 'Reset OP' operand, a warning can appear indicating that this is a disabled feature. This means that the
Reset Settting's FlexLogic operand is set to OFF. Resetting of the relay can be done by pressing the reset button on the front
panel of the relay or by sending a Reset command through communications.
Table 4-4: Warning messages from compiling
4.4.1.5 Rapidly add logic blocks in sequence
Blocks are added by clicking an element then clicking in the drawing area, or by dragging and dropping the element onto
the canvas. Blocks can be added rapidly in sequence, for example when you have inputs 1 to 10, without having to select
the element each time.
To rapidly add logic blocks:
1.
In Engineer, click
File > Preferences
. The window opens.
2.
Click the
Editor
entry.
3.
Enable the
Repeat Symbol
check box.
4.
Click the
Ok
button to save and exit from the window.
5.
In the logic diagram, select an element, then click in the drawing area to add it, click again to add a second box, and
so on.
Error
Timer
Timer used more than once
(TIMER_ID, SheetReference)
The same timer is used in more than one place in the editor. This means
either the circuit that the Timer belongs to has been branched, or the
Timer has been duplicated.
Error
Input
Unrecognized Parameter
(SYMBOL_ID,Name,SheetRefere
nce)
An Input symbol is configured to an item that is not recognized by the
current order code and version. Possible cause: The order code and/or
version of the settings file was converted causing the input parameter to
become unavailable.
Category
Block or
gate
affected
Message
Description
Minor warning
Input
Input set to unused VO
(SYMBOL_ID,Name,Sheet)
An Input symbol is using an unassigned Virtual Output
Major warning
Tag-Out
Tag-out not connected
(TAG_ID,Sheet)
A Tag-Out symbol has no input
Major warning
All
Symbol not connected
(SYMBOL_ID,Name,Sheet)
A symbol’s input and/or output is not connected and is not part of a
VO block. Draw the input and/or output to the block.
Minor warning
=VO
Virtual Output n using default
name (VO_ID,Sheet)
The Assigned Virtual Output is using the default name. Change the
name.
Minor warning
Input
Input using default name
(SYMBOL_ID,Name,Sheet)
An Input symbol is using a Contact Input, Contact Output, Digital
Element, FlexElement, or Digital Counter set to the default name.
Change the name so that it is unique.
Setting warning
Input
Input using disabled feature
(SYMBOL_ID,Name,Sheet)
An Input symbol is using a disabled Virtual Input, Contact Input, Digital
Element, FlexElement, Digital Counter, Control Pushbutton,
Programmable Pushbutton, Contact Output, or Protection/Monitoring
Element. Enable it and try again.
Major warning
Input
Input set to OFF
(SYMBOL_ID,Sheet)
An Input symbol is set to OFF
Major warning
Input
Input set to ON
(SYMBOL_ID,Sheet)
An Input symbol is set to ON
Setting warning
Input
Contact Output Operate is OFF
(SYMBOL_ID, Contacts)
The symbol block is using the default setting of OFF
Setting warning
Input
Contact Output Seal-In is OFF
(SYMBOL_ID, Contacts)
The symbol block is using the default setting of OFF
Category
Block or gate
affected
Message
Description