![GE Kelman DGA900 Operator'S Manual Download Page 76](http://html.mh-extra.com/html/ge/kelman-dga900/kelman-dga900_operators-manual_128395076.webp)
MA-025
–
DGA 900 Operator Guide
–
Rev 2.0
12-Apr-19
Page 76 of 92
▪
Pull each pin forward and out to remove it from the vibration mount assembly as shown
in Figure B-3.
Figure B-3: PGA lock
–
remove pins
▪
Loosen and remove the two plastic nuts securing the metal bracket to the anti-
vibration mounts as shown in Figure B-4.
Figure B-4: PGA lock
–
remove plastic nuts
▪
Remove the metal bracket as shown in Figure B-5.
Note: Retain the metal bracket, pins
and plastic nuts for future use of the lock.
Figure B-5: PGA lock
–
remove metal bracket
The transportation PGA lock is now disengaged rendering the PGA anti-vibration mounts
active. If the product is transported and reconnected to a different substation asset, it
must be recommissioned by a GE-approved commissioning engineer.