2.2 Environmental Specifications
Note:
Install the QuickPanel
+
in a well-ventilated
location that is not exposed to dust,
corrosive gases or liquids, rain, strong ultra-
violet light or direct sunlight, and meets the
following specifications.
Item
Specification (All Display Units)
Cooling
Natural convection
Ambient Operating
Temperature
0 to +55°C (32 to 131 °F)
Ambient Storage
Temperature
-10 to +60°C (14 to 140 °F)
Ambient Humidity
(Operating/Storage)
85% RH Non-condensing, wet-bulb
temperature: 30°C (86 °F) or less
Environment
Pollution Degree 2, Indoor use only
Vibration
Resistance
5 to 9 Hz single-amplitude 3.5 mm
9 to 150 Hz constant-accelerated
velocity 9.8 m/s
2
; X, Y, Z directions 10
time (100 minutes)
(Compliance 3502, IEC61131-2 JIS B)
Altitude
800~1114 hPa, altitude up to 2000 m
(6561.68 ft)
RoHS
Compliant with EU RoHS Directive
2011/65/EU
Enclosure Rating
IC755CxS06RDx:
UL Type 4X;
IP65 in panel mount only
IC755CxW07CDx:
UL Type 4X;
IP65 in panel mount only
IC755CxS10CDx:
UL Type 4X;
IP65 in panel mount only
IC755CxS12CDx:
UL Type 4X;
IP65 in panel mount only
IC755CxS15CDx:
UL Type 4X;
IP65 in panel mount only
Note:
For additional product standards and agency
approvals, refer the section
Product
Certifications and Installation Guidelines
.