RX3i Ethernet Interface Module IC695ETM001-HV IPI 

GFK-2332W 

February 2016 

 

Important Product Information for this Release 

This hardware release addresses a component obsolescence issue. There are no changes to form, fit, or function. 

Updates 

The IC695ETM001 is field upgradeable using the firmware upgrade utility. To upgrade an existing ETM001 to 

firmware version 6.31, you will need the upgrade kit 44A753032-G18, which can be downloaded from 

http://www.ge-ip.com/support. 

The hardware cannot be upgraded in the field. 

Functional Compatibility 

Functional Compatibility 

Subject 

Description 

Hot Swap requires CPU 

firmware 2.51 

Do not remove or insert the IC695ETM001 while powered unless the CPU is 

running firmware release 2.51 or higher. This firmware is available in upgrade kit 

44A7522290-G01. 

SRTP and EGD 

performance differs 

from Series 90*-30 

SRTP and EGD performance in the RX3i differs slightly from the Series 90-30. Each 

RX3i Ethernet Interface supports a greater number of SRTP connections and EGD 

exchanges. 
The RX3i currently has several SRTP and EGD operational restrictions compared 

to the Series 90-30. When migrating Series 90-30 Ethernet applications to the 

RX3i, please carefully read the 

Ethernet Operational Notes

Series 90-30 LAN 

Interface module 

(IC693CMM321) not 

supported by RX3i 

The Series 90-30 LAN Interface Module (IC693CMM321) is not supported by the 

RX3i and should not be placed in an RX3i rack.  (Series 90-30 CPUs with 

embedded LAN Interface, IC693CPU364 and IC693CPU374, like any Series 90-30 

CPU, should not be placed in an RX3i rack.)  

Modbus/TCP support 

Release 3.60 of the PACSystems Ethernet Interface adds Modbus/TCP Client 

Channels capability.  It supports Modbus Conformance Class 0 function codes 3 

and 16, Conformance Class 1 function codes 1, 2, 4, 5, 6, and 7, and Conformance 

Class 2 function codes 15, 22, 23, and 24.  PACSystems Ethernet supports 32 

client connections shared between all client protocols.  For example, if 16 client 

connections are used for SRTP channels, there are 16 client connections available 

for Modbus/TCP channels.  Any given channel can be assigned to only one 

protocol at a time. 

Programmer version 

requirements 

Proficy* Machine Edition Logic Developer 5.8 or later must be used to perform 

Run-mode Store of EGD exchanges. 
Proficy Machine Edition Logic Developer 5.7 or later must be used for Release 

5.00 new features. 
Proficy Machine Edition Logic Developer 5.5 Service Pack 2 or later must be used 

for Release 4.00 new features. 
Proficy Machine Edition Logic Developer 5.0 Service Pack 3 or later must be used 

to program the RX3i CPU for Modbus/TCP Server operation. 

CIMPLICITY

*

 Plant 

Edition version 

requirements 

CIMPLICITY Plant Edition 6.1 Service Pack 1a with Update 040204_s90tcp_6101 or 

Service Pack 2 or later must be used for Ethernet communications with 

PACSystems. 

New Features and Enhancements in This Release 

An enhancement was made to prevent the module from becoming unresponsive and requiring a power cycle if it was 

subjected to heavy network storm traffic. Reference: GE Security Advisory is GE15-09, titled 

Network Storm Denial of 

Service

 

 

Summary of Contents for IC695ETM001

Page 1: ... Server and Modbus TCP Client Built in Station Manager for on line supervisory access to the Ethernet Interface Dedicated Station Manager port Two auto sensing 10Base T 100Base TX RJ 45 shielded twisted pair Ethernet ports for direct connection to either a 10BaseT or 100BaseTX IEEE 802 3 network without an external transceiver There is only one interface to the network only one Ethernet MAC addres...

Page 2: ...tion Manager Port RS 232 DCE 1200 115 200 bps Refer to the PACSystems RX3i System Manual GFK 2314 for product standards and general specifications Ethernet Interface Status Bits Note Unless LAN Interface OK Status Bit 16 is set the other status bits are invalid LAN Interface Status Bits 1 Port 1A full duplex 2 Port 1A 100Mbps 3 Port 1B full duplex 4 Port 1B 100 Mbps 5 Network Time Locked 6 Redunda...

Page 3: ...l ETHERNET OK LAN OK LOG EMPTY Blink error code Off Off Hardware failure See chapter 11 for blink code definitions ETHERNET OK LAN OK LOG EMPTY Slow Blink Slow Blink Slow Blink All LEDs blink in unison pattern same while awaiting or performing load Firmware Update Field Wiring Station Manager RS 232 Port Pin Assignment Pin No Signal Direction Description 1 DCD IN Data Carrier Detect 2 TX OUT Trans...

Page 4: ...he enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This equates to a NEMA UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a pollution degree 2 environment For details about installing RX3i rack systems refer to GFK 2314 If you need technical help contact Technical Support For phone numbers and email addresses see the back cover of...

Page 5: ...odule to be sure it is properly seated 3 Insert the two provided M3x5mm machine screws through the module s bottom bracket into threaded holes in the bottom of the backplate and screw them several turns using a 1 Phillips screwdriver Tighten to 0 7 N m 6 in lbs Related Documents For additional information about the Ethernet Interface Module refer to the following publications GFK 2314 PACSystems R...

Page 6: ...d LAN Interface IC693CPU364 and IC693CPU374 like any Series 90 30 CPU should not be placed in an RX3i rack Modbus TCP support Release 3 60 of the PACSystems Ethernet Interface adds Modbus TCP Client Channels capability It supports Modbus Conformance Class 0 function codes 3 and 16 Conformance Class 1 function codes 1 2 4 5 6 and 7 and Conformance Class 2 function codes 15 22 23 and 24 PACSystems E...

Page 7: ...to the supplied value Release History Release History Catalog Number Firmware Version Date Comments IC695ETM001 HV 6 40 Feb 2016 An enhancement was made to prevent the module from becoming unresponsive and requiring a power cycle if it was subjected to heavy network storm traffic Reference GE Security Advisory is GE15 09 titled Network Storm Denial of Service In addition to the enhancement there w...

Page 8: ... change to the module s firmware or functionality IC695ETM001 ES 6 21 Jan 2014 Ethernet Firmware version fixes an issue with calculating DST correction in the European Union when SNTP is enabled IC695ETM001 ER 6 20 Jul 2013 Adds support in SNTP for local time zones and daylight savings time and resolves the field issues described on page 7 IC695ETM001 EP 6 14 Jul 2012 Resolves an issue with a spur...

Page 9: ...he connections SRTP connections remain open after IP address changed The Ethernet Interface does not terminate all open SRTP connections before changing its IP address If the local IP address has changed any existing open TCP connections are unable to normally terminate This can leave SRTP connections open until their underlying TCP connections time out If quicker recovery of the SRTP connection i...

Page 10: ...ault can be safely ignored Unexpected EGD COMMREQ status EGD Commands may return COMMREQ Status 9590H internal error instead of the expected B190H Can t locate remote node when unable to locate a remote device on the network Very heavy EGD production consumption at server may cause EGD command timeouts Very heavy EGD production and or consumption at a server device may cause EGD command timeout er...

Page 11: ...eference memory sizes at the appropriate PLC Do not operate with CPU in incorrect slot The operation of the Ethernet interface is disrupted if the RX3i CPU is placed in a slot other than the one in which it is configured Various Ethernet exception log events may occur such as Entry 2 Entry 2 30 or 35 or 39 or 1e or 1f or Entry 8 Entry 2 b No CPU fault logged when Ethernet interface in fatal blink ...

Page 12: ...o the parent directory then delete the target directory without specifying a path For example the rmdir dir1 dir2 results in RMDIR Failed dir1 dir2 does not exist Instead first do cd dir1 and then rmdir dir2 Intermittent Ethernet log event 8H 15H after power cycle When starting after a power cycle the Ethernet Interface may intermittently log an exception entry 8H Entry 2 15H Entry 3 0000H Entry 4...

Page 13: ...s is disabled until the station manager password is changed to other than the default password The station manager password can be changed using an AUP file Refer to Appendix A Configuring Advanced User Parameters in TCP IP Ethernet Communications for PACSystems User s Manual GFK 2224K Changing the default Station Manager password is strongly recommended GE Intelligent Platforms strongly recommend...

Page 14: ...ress from a BOOTP server device on the network LAN must be tree not ring The two Ethernet network ports on the PACSystems RX3i Ethernet Interface must not be connected directly or indirectly to the same network device The hub or switch connections in an Ethernet network must form a tree and not a ring otherwise duplication of packets and network overload may result In this situation the RX3i Ether...

Page 15: ...ntain the underlying network and STRP connection Examples are establishing the TCP connection for a new channel establishing communication with the remote device and TCP retransmissions during Channel operations If the time needed for TCP connection establishment or maintenance exceeds the user specified channel application timeout values an application timeout will occur Channel application timeo...

Page 16: ...net interface time via the CHTIME command does not affect the timestamp value within EGD exchanges produced from this Ethernet interface The EGD timestamp value reflects the current CPU time In Series 90 70 products and the Series 90 30 CPU364 EGD timestamps are taken from the Ethernet interface and do reflect CHTIME modifications ENIU Stale Data During Run Mode Store of EGD In a large PPS system ...

Reviews: