ADJUSTABLE FEATURES
SX TRANSISTOR CONTROLS
Page 32
May 2002
FUNCTION 5
PLUG CURRENT LIMIT
(Push
5)
This function allows for the adjustment of the maximum
current allowed during plug braking.
Range
26 to 225 amps
Set
0 to 255
Resolution
0.8125 amps per unit
Example
Setting of 20 = 26 + (20 X .8125) =
42
Amps
FUNCTION 6
ARMATURE ACCELERATION RATE
REVERSE (OR FORWARD IN TURF MODE)
(Push
6)
This function allows for the adjustment of the rate of time it
takes for the control to accelerate to 100% applied battery
voltage to the motor on hard acceleration in the reverse
direction. (or in the forward direction in turf mode)
Range
0.1 to 25.5 seconds
Set
1 to 255
Resolution
0.086 seconds per set unit
Example:
Setting of 29 = 29 x 0.086 = 2.5 seconds
FUNCTION 7
MIN. FIELD CURRENT
( Push 7 )
This function allows the adjustment of the field weakening
level in order to set the top speed of the motor.
Range
0 to 32 amps
Set
51 to 255
Resolution
0.16 amps per set unit
Example
Setting of 73 = (73-51)x0.16 = 3..5 amps
CAUTION: Do not set this function to a value less than 51.
Important Note: The function is used to optimize motor and
control performance and this setting will be determined by
GE and OEM engineers at the time of vehicle development.
This setting must not be changed by field personnel without
the permission of the OEM.
FUNCTION 8
MAX FIELD CURRENT
( Push 8 )
This function allows for the adjustment of the maximum
field current in order to obtain the maximum torque of the
motor.
Range
0 to 32 amps
Set
51 to 255
Resolution
0.16 amps per set unit
Example
Setting of 251=(251–51)x0.16
= 32 amps
CAUTION: Do not set this function to a value less than 51.
Important Note: The function is used to optimize motor and
control performance and this setting will be determined by
GE and OEM engineers at the time of vehicle development.
This setting must not be changed by field personnel without
the permission of the OEM.
FUNCTION 9
REGEN ARMATURE CURRENT LIMIT
(Push
9)
This function allows for the adjustment of the maximum
armature current limit during regenerative braking.
Range
32 to 240 amps
Set
1 to 255
Resolution
0.8157 amps per set unit
Example
Setting of 221 = (221x0.8157) +32
= 212 amps
FUNCTION 10
REGEN FIELD CURRENT LIMIT
( Push 10 )
This function allows for the adjustment of the maximum
field current limit during regenerative braking.
Range
0 to 32 amps
Set
51 to 255
Resolution
0.16 amps per set unit
Example
Setting of 180 = (180-51)x0.16
= 20.6 amps
CAUTION: Do not set this function to a value less than 51.
Important Note: The function is used to optimize motor and
control performance and this setting will be determined by
GE and OEM engineers at the time of vehicle development.
This setting must not be changed by field personnel without
the permission of the OEM.
FUNCTION 11
TURF SPEED LIMIT
(Push
11)
This function allows for the adjustment of the top speed of
the vehicle (maximum battery volts to the motor) when it is
in Turf Mode.
Range
100% to 0% (or creep speed)
Set
51 to 170
Resolution
0.78% per set unit