Page 43
Hydran* M2-X Installation Guide
MA-028
Rev. 2.1,
11-Jun-20
Press Escape button to
go back to
Configuration
.
Select
Readings Setup
Press
Enter
Set up all the
Readings
Setup
parameters as
required.
Notes:
•
Input Min
is the lowest possible reading for this signal; this value corresponds
to 4 mA.
•
Input Max
is the highest possible reading for this signal; this value
corresponds to 20 mA.
•
Repeat the above procedure for each analog input that is installed.