NE-M Installation Guide
H5692448
850050111
Issue 03 August 2017
53
Step
Action – Pulsar Plus
4
Output Alarm Connector
Connect and wire remote alarm output circuits to Connector J4. J4 is output alarm connector.
Utilize cable as necessary to obtain the desired connections to the outputs shown below.
Output Alarm Cable comcodes for J4 are: 50ft: CC848817635, 150ft: CC848817643.
Table 6 Alarm Signals - Pulsar Plus
Pin
Wire
Signal
Name
Pin
Wire
Signal
Name
Defaults
Standard
Eco
1
BL
PCR
11
BL/BK
PCR_C
PCR
(Power Critical)
2
O
PMJ
12
O/BK
PMJ_C
PMJ
(Power Major)
3
G
PMN
13
G/BK
PMN_C
PMN
(Power Minor)
4
W
UR1
14
W/BK
UR1_C
BD
(Battery on
Discharge)
5
BK
UR2
15
BK/W
UR2_C
VLV
(Very Low Voltage)
6
BL/W
UR3
16
BL/R
UR3_C
FAJ
(External Fuse Major)
7
O/R
UR4
17
R
UR4_C
ACF
(rectifier input AC or
DC) Fail)
Generator
Start/Stop
8
G/W
UR5
18
R/G
UR5_C
RFA
(Rectifier Fail)
9
W/R
UR6
19
R/W
UR6_C
MRFA
(Multi Rectifier Fail)
10 BK/R
UR7
20
R/BK
UR7_C
HV
(High Voltage)
Generator
Maintenance
5
Network (LAN) Connection (Optional)
Connect to network.
The controller provides an Ethernet connection for a LAN and or Craft port connection. Connector
J5
provides a
standard RJ45 shielded receptacle connection for a standard Cat-5 connection to the controller’s 10/100Base-T
port. This port has two main modes of operation: Server mode, LAN mode (Static and DCHP Client). In server
mode, the port can be used as a local Craft interface. In this mode, a local laptop can be connected through
J5
and its standard web browser used to directly access the controller by typing in network address
http://192.168.2.1. A connection should never be made between the controller and LAN while the controller is in
Server mode.
Is the controller equipped with the Modem Option?
Yes – go to Step 6.
No – go to Step 7.
19
Relays are reconfigured for specific use for specific Eco applications.