10
Installation Instructions
CONNECTING DRYER USING
3-WIRE CONNECTION
24” MODELS - CONNECTING AN ELECTRIC DRYER
3-wire Connection
NOT for use in Canada.
DO NOT use for Mobile Home Installations.
NOT for use on new construction.
NOT for use on recreational vehicles.
NOT for use in areas where local codes prohibit
grounding through the neutral conduction.
CONNECTING DRYER USING 4-WIRE
CONNECTION (MUST BE USED FOR
MOBILE HOME INSTALLATION)
NOTE:
Since January 1, 1996, the National Electrical
Code requires that new constructions use a 4-wire
connection to an electric dryer. A 4-wire cord must also
be used where local codes do not permit grounding
through the neutral.
3-wire connection is NOT for use on new construction.
1.
Turn off the circuit breaker(s) (30 amp) or remove
the dryer’s circuit fuse at the electrical box.
2.
Be sure the dryer cord is unplugged from the wall
receptacle.
3.
Remove the power cord cover located at the lower
back.
4.
Remove and discard ground strap. Keep the green
ground screw for Step 7.
5.
Install 3/4 in. UL-recognized strain relief to power
cord entry hole. Bring power cord through strain
relief.
6.
Connect power cord as follows:
A.
Connect the 2 hot lines to the outer screws of the
terminal block (marked L1 and L2).
B.
Connect the neutral (white) line to the center of
the terminal block (marked N).
7.
Attach ground wire of power cord with the green
ground screw (hole above strain relief bracket).
Tighten all terminal block screws (3) securely.
8.
Properly secure power cord to strain relief.
9.
Reinstall the cover.
NEVER LEAVE THE COVER OFF OF THE
TERMINAL BLOCK.
NEVER LEAVE THE COVER OFF OF THE
TERMINAL BLOCK.
L1
N
L2
RELOCATE GREEN
GROUND SCREW
HERE
STRAIN
RELIEF
BRACKET
GREEN OR
YELLOW WIRE
3/4", UL
RECOGNIZED
STRAIN RELIEF
HOT
WIRE
SCREWS
(3)
HOT WIRE
COVER
NEUTRAL
(White)
REMOVE GROUND
STRAP AND DISCARD.
KEEP GREEN
GROUND
SCREW
4 #10 AWG MINIMUM COPPER
CONDUCTORS OR 120/240V 30A POWER
SUPPLY CORD KIT MARKED FOR USE
WITH DRYERS & PROVIDED WITH
CLOSED LOOP OR SPADE TERMINALS
WITH UPTURNED ENDS (NOT SUPPLIED).
L1
L2
STRAIN RELIEF
BRACKET
3/4", UL
RECOGNIZED
STRAIN RELIEF
HOT
WIRE
HOT
WIRE
GROUND
STRAP
GREEN
GROUND
SCREW
NEUTRAL
(White)
SCREWS
(3)
COVER
3 #10 AWG MINIMUM COPPER
CONDUCTORS OR 120/240V 30A POWER
SUPPLY CORD KIT MARKED FOR USE
WITH DRYERS & PROVIDED WITH
CLOSED LOOP OR SPADE TERMINALS
WITH UPTURNED ENDS (NOT SUPPLIED).
1.
Turn off the circuit breaker(s) (30 amp) or remove
the dryer’s circuit fuse at the electrical box.
2.
Be sure the dryer cord is unplugged from the wall
receptacle.
3.
Remove the power cord cover located at the lower
back.
4.
Install 3/4-in. UL-recognized strain relief to power
cord entry hole. Bring power cord through strain
relief.
5.
Connect power cord as follows:
A.
Connect the 2 hot lines to the outer screws of the
terminal block (marked L1 and L2).
B.
Connect the neutral (white) line to the center of
the terminal block (marked N).
6.
Be sure ground strap is connected to neutral
(center) terminal of block and to green ground
screw on cabinet rear. Tighten all terminal block
screws (3) securely.
7.
Properly secure power cord to strain relief.
8.
Reinstall the cover.
Summary of Contents for GUD27ESSMWW
Page 18: ...18 Notes ...
Page 19: ...19 Notes ...
Page 20: ...20 Printed in Mexico ...
Page 38: ...Notes 18 ...
Page 39: ...19 Notes ...
Page 40: ...20 Imprimé au Mexique ...
Page 58: ...Notas 18 ...
Page 59: ...19 Notas ...
Page 60: ...20 ...