Service diagnosis
42
Domestic air conditioner
10.3.8 Power Supply Over or under voltage fault
Outdoor display: LED1 flash 6 times The power supply is over voltage
Method of An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit.
Malfunction
Detection
Malfunction An voltage signal is fed from the voltage detection circuit to the microcomputer
Decision
Conditions
Supposed
Ŷ
Supply voltage not as specified
Causes
Ŷ
the IPM module is broken
Ŷ
the outdoor PCB is broken
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Electrify the machine again and turn it on with
the remote controller. Check whether the
compressor is started normally
Is it ok?
Yes
Maybe there is some disturbance
NO
No
~230 is ok?
Yes
Yes
This question may be caused by the power. Repair
the power supply.
NO
Change the IPM module
Change the IPM module
Test the outdoor power supply
(+310VDC) with a multimeter.
check whether the power
is >150 V or <390V?
Summary of Contents for GES-NX2G50OUT
Page 11: ...Pinping diagrams Domestic air conditioner 4ˊPiping diagrams 9 EEV EEV ...
Page 12: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Page 58: ...Circuit diagrams 56 Domestic air conditioner 12 Circuit diagrams ...
Page 59: ...Circuit diagrams 57 Domestic air conditioner ...
Page 62: ...Domestic air conditioner Removal of procedure 1 Removal of Outdoor panel 1 ...
Page 64: ...Domestic air conditioner Loosen the screws and pull the panel Removal of procedure 3 ...
Page 65: ...Domestic air conditioner 2 Removal of Electrical Box Removal of procedure 4 ...
Page 66: ...Domestic air conditioner 3 Removal of Fan and Fan Motor Removal of procedure 5 ...
Page 68: ...Domestic air conditioner 4 Removal of Fan Motor Bracket and Partition Removal of procedure 7 ...
Page 69: ...Domestic air conditioner and remove the reactor Loosen the screw Removal of procedure 8 ...