Service diagnosis
Domestic air conditioner
10 Service Diagnosis
10.1 Caution for Diagnosis
The operation lamp flashes when any of the following errors is detected.
1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions,
disabling equipment operation.
2. When a signal transmission error occurs between the indoor and outdoor units. In either case, conduct the
diagnostic procedure described in the following pages.
Parameter of primary electronic appliance
e
r
u
t
c
i
p
r
e
t
e
m
a
r
a
p
e
m
a
n
Compressor
Rated voltage:220-230V
Rated current:4.8A
Rated frequency: 50/60HZ
Fan motor
Rated voltage:220-230V
Rated current:0.2A
Rated frequency: 50/60HZ
Reactor
Rated voltage:220-230V
Rated current:10.5A
Rated frequency: 50/60HZ
4-way valve
Rated voltage:220-230V
Rated current:0.1A
Rated frequency: 50/60HZ
30
Summary of Contents for GES-NX2G35OUT
Page 11: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 ...
Page 12: ...Operation range Domestic air conditioner 5 Operation range 10 ...
Page 39: ...Service diagnosis 37 Domestic air conditioner ...
Page 61: ...Removal Procedure 1 Removal of Outdoor Panel ...
Page 62: ...Removal Procedure n o i t i d n o C r i A c i t s e m o D 2 ...
Page 63: ...4 Removal Procedure 3 Domestic Air Condition ...
Page 64: ...Removal Procedure 2 Removal of Electrical Box RPHVWLF LU RQGLWLR ...
Page 65: ...Removal Procedure 3 Removal of Fan and Fan Motor RPHVWLF LU RQGLWLR ...
Page 66: ...Removal Procedure 4 Removal of Fan Motor Brcked and Partition ...
Page 67: ...Removal Procedure 7 Domestic Air Condition ...
Page 68: ...Removal Procedure 5 Removal of Compressor and Heat Exchanger ...