5.5 Precaution For Initial Startup
1. Make sure the AC circuit is connected and the AC breaker is turned off.
2. Make sure the DC cable between inverter and PV string is connected, and the PV voltage is
normal.
3. Turn on the DC switch, and set safety country according to the local regulation.
4. Turn on the AC breaker. Check the inverter work is working normally.
5.6 Special Adjustable Setpoints(Only for Australia and New
Zealand)
The inverter has a field in which the user can set functions, such as trip points, trip times, reconnect
times, active and inactive QU curves and PU curves. It is adjustable through special software. If
needed, please contact after-sales. To obtain software manuals, you can download them from the
official website or contact after-sales.
5.6.1 PF Power Curve Mode
PF power curve mode can be modified by Modbus communication method, specifically according
to the inverter Modbus address and Modbus register value, according to the set range in the set
the corresponding value.
A
B
C
Power, (%P/P
rated
)
1.0
0.95
0.95
0%
25%
50%
75%
100%
cosФ
LEGEND:
cosФ
LEADING
LAGGING
5.6.2 PU Curve Mode
The PU curve mode can be modified by Modbus communication method, specifically according
to the inverter Modbus address and Modbus register value, according to the set range to set the
corresponding value.
PF Power Curve Mode
Function
PF curve mode enable or disable
B %P/Prated
C Power factor
Default value (Australia)
0
50 (50%)
0.9
Default value (New Zealand)
0
50 (50%)
0.9
Setting range
“0”or“1”
30%~80%
0.8~1
Register
40600
40603
40606
V1
V2
V3
V4
V1
V2
V3
V4
100%
80%
60%
40%
20%
0%
200
210
220
230
240
250
260
270
POWER, P/Prated%
100%
80%
60%
40%
20%
0%
200
210
220
230
240
250
260
270
POWER, P/Prated%
Example curve for a volt-watt response mode (Australia)
Example curve for a volt-watt response mode (New Zealand)
PU curve Mode
Function
PU curve mode enable or disable
V1 voltage ratio
P1 power ratio
V2 voltage ratio
P2 power ratio
V3 voltage ratio
P3 power ratio
V4 voltage ratio
P4 power ratio
Default value (Australia)
1
900 (207V)
1000 (100%*Pn)
956 (220V)
1000 (100%*Pn)
1087 (250V)
1000 (100%*Pn)
1152 (265V)
200 (20%*Pn)
Default value (New Zealand)
1
900 (207V)
1000 (100%*Pn)
956 (220V)
1000 (100%*Pn)
1061 (244V)
1000 (100%*Pn)
1109 (255V)
200 (20%*Pn)
Setting range
““0”or“1”
0~2000
0~1500
0~2000
0~1500
0~2000
0~1500
0~2000
0~1500
Register
40680
40683
40684
40685
40686
40688
40689
40690
40691
Example: Set the ratio of V1 voltage to 1100, corresponding to the rated voltage of 230 V, V1
=
230
* 110% = 253 V.
Example: Set P1 power ratio to 900 and the corresponding power to 0.9* rated power.
23
24