background image

Figure 

3. 

Mechanical counter  installed  in breaker. 

9. 

Reinstall  the  breaker  top  cover,  ensuring  that  the 

Trip  Unit  and  aluminum  accessory  sleeve  are 

properly  aligned  with  the  cover.  Tighten  the  four 

#10-32 

screws to 

32 

in-lbs. 

10. 

Replace  the  trim  plate  and  tighten  the  four 

#8-32 

screws  to 

20 

in-lbs. 

11. 

If  it  is  a  draw-out  breaker,  rack  it  back  in. 

__ 

Possible  Cause 

12., 

Apply  control  power  to  the  accessories,  then 
follow  the  normal  procedure  to  recharge  the 

springs  and  tum  the  breaker  on. 

Trouble-Shooting 

The  following  guide  is  provided  for  trouble-shooting 

and  isolating  common  problems.  It  does  not  cover  every 

possible situation.  Contact  the  ED&C  Customer  Support 
Center at 

800-843-3742 

if  any  problem  is  not  resolved  by 

these  procedures. 

Partially Obscure  Counter Display 

Figure 

4. 

Counter partially obscured  in  top  cover  window. 

Corrective Action 

The 

Mechanical  Counter  does 

not  advance  with  operation  of 
the  breaker. 

The  spring-loaded  Mechanical 
Counter  arm  is  not  above  the  tab  on 
the  ON-OFF  flag. 

See  step 

of  the  installation  instructions. 

The  first  digit  of  the 

Mechanical  Counter  is  partially 

obscured  in  the  top  cover 
window,  as  in  Figure 

4. 

The  Mechanical  Counter  is  out  of 
adjustment  on  the  mounting  plate. 

Measure  the  interference.  Remove  the 

breaker  top  cover  and  the  Mechanical 

Counter  assembly.  Loosen  the  two  screws 
holding  the  Counter  to  the  mounting 
plate.  Slide  the  Counter  over  by  the 
amount  of  the  interference.  Tighten  the 

two  Counter  mounting  screws  to 

10 

in-lbs, 

then reinstall  the  Counter  as  per  the 
installation  instructions. 

These  instructions  do  not  cover  all  details  or  variations  in  equipment  nor  do  they  provide  for  every  possible 

contingency  that  may  be  met  in  connection  with  installation,  operation,  or  maintenance.  Should  further 

information  be  desired  or  should  particular  problems  arise  that  are  not  covered  sufficiently  for  the 

purchaser's  purposes,  the  matter  should  be  referred  to  the  GE  Company. 

GE  Electrical  Distribution  &  Control 

General  Electric Company 

41 Woodford Ave.,  Plainville,  CT 06062 