GEH-62808 

Power  Break®  II  Circuit  Breaker 

Accessories 

Mechanical  Counter 

Introduction 

The  Mechanical  Counter,  shown  in  Figure 

1, 

can  be 

installed  in 

800-4000 

ampere  frame  Power  Break®  II 

circuit  breakers.  Its  function  is  to  count  the  number  of 

times  the  breaker  is  closed.  The  catalog  number  when 

ordered  with  a  circuit  breaker  for  factory  installation  is 

SPCOUNTER.  The  catalog  number  of  the  field­
installable  Mechanical  Counter  kit  is  SPCOUNTERR. 

Figure 

1. 

Mechanical  Counter. 

Operation 

The  count  displayed  by  the  Mechanical  Counter  is 
incremented  each time the  circuit  breaker  is  closed. 

Installation 

WARNING: 

Before  installing  any  accessories,  turn  the 

breaker  OFF,  disconnect  it  from  all  voltage  sources,  and 

discharge  the  closing  springs. 

AVERTISSEMENT: 

Avant  d'installer  tout  accessoire, 

mettre  le  disjoncteur  en  position  OFF,  le  deconnecter 

de  toute  tension  d'alimentation,  et  decharger  les 
ressorts  d'armement 

Install  the  Mechanical  Counter  with  the  following 

procedure. 

1. 

Turn  off  the  breaker,  discharge  the  springs,  and 

turn  off  control  power  to  the  accessories  and 
motor  operator  (if  present).  If  it  is  a  draw-out 
breaker,  rack  it  out. 

2. 

Loosen  the  four 

#8-32 

screws  on  the  trim-plate 

assembly  and  remove  the  trim  plate. 

3. 

Loosen  the  four  screws  at  the  corners  of  the 
breaker  cover.  Remove  the  cover  from  the  breaker 
face. 

4. 

On the  breaker  cover,  use  a  screwdriver  to  punch 

out the  knockout  above  the 

CHARGE-DISCHARGE 

flag  opening. 

5. 

Hold  the  ON-OFF  flag  towards  the  ON  position, 
then carefully  insert  the flag lockout plate to retain 
the  flag  in  this  position.  The  flag  lockout  plate 
should  be  installed  close  to  the  side  frame  on 
which  the 

ON-OFF 

flag  pivots  and  over  the  larger 

diameter  portion  of  the  mechanism  cross  pin. 
The  installed flag  lockout  plate  is  shown  in  Figure 

2. 

LOCKOUT 

PLATE 

Figure 

2. 

Flag lockout plate installed in breaker. 

6. 

Locate  the  two  mounting  holes  through  the  side 
frame,  behind  the 

CHARGE-DISCHARGE 

flag. 

Place  the  spring-loaded  Mechanical  Counter  arm 
above  the  tab  on  the 

ON-OFF 

flag,  while 

simultaneously  inserting  the  two  pins  on  the 
Mechanical  Counter  through  the  holes  in  the  side 
frame. 

7. 

Slide  the straight  legs  of  the  provided  clip  over  the 

pin  on  the  Mechanical  Counter  furthest  from  the 

ON-OFF 

flag.  Rotate  the  clip  counter-clockwise 

until  the  circular  part  of  the  clip  snaps  over  the 
second  pin  on  the  Mechanical  Counter. 

8. 

Carefully  remove  the  flag  lockout  plate,  allowing 
the 

ON-OFF 

flag to return  to the 

OFF 

position.  The 

installed Mechanical Counter  is  shown  in  Figure 

3. 