GE Security
FHSD700C Series Product Guide
5.3.8 SETUP: Setup Menu
Minimum Access Code Required:
Level 2
Once the Setup Mode is accessed, please follow this procedure to change a parameter:
1. Press
Parameter
UP
&
DOWN
buttons to reach required
SETUP
item.
2. Press
ENTER
.
3. Press
Value
UP
&
DOWN
buttons to update the item.
4. Press
ENTER
to update and move to next parameter. If the value is left unchanged,
ENTER
will
have no effect.
Press
MENU
to get back to the Main Menu. Press
MENU
again to get back to Normal display.
The Setup menu has the following items.
Table 5-6: Setup Menu Parameters and Values
Parameter
Value Defaults
Description
HI RESLTN
0, 1, 2
or 3
0
Enables the Status Display to show standard resolution (0) or higher Resolution
(1, 2 or 3) for obscuration (switches between a resolution of 0.01 to 0.00001).
Note
: It is highly recommended to leave this value at 0. Changing the value from
0 will cause some configuration values to change. Connection to GE Security
fire configuration and management software will automatically change this value
back to 0.
OBSC/FT
0 or 1
0
Set to 1 to display smoke valve in % obs/ft. Normally % obs/m.
REMPANEL 0 or 1
0
Enables remote panel operation. A communications fault will be displayed if this
is enabled without a remote display connected.
REMPOD
0 or 1
0
Set to 1 if a Remote Sensing Unit is connected.
Note
: This option is not available for standard FHSD700C devices.
DETFLOW
0 or 1
1
In addition to individual sector flow monitoring, detector flow monitoring is also
incorporated.
Set to 1 to enable.
CCODE
Country Code
See Table 5-7. Changes metric/imperial units.
RES-ISOL
0 or 1
1
Set to 1 to reset system with 24 V on reset line.
Set to 0 to isolate system when 24 V is applied for 8 seconds or more.
MOD1 to 5 List of available I/O
modules
All I/O modules fitted at build will have this information entered. If additional I/O
modules are installed, their type must be entered here.
The FHSD700C detector can operate in a number of different languages. To change the language, the
correct country code (CCODE) must be entered. The software can also be made to swap from metric to
imperial measurements by entering 1 for the United States country code.
Table 5-7: Country Codes for the FHSD700C Series
Language
Code
English (default)
44
United States (English)
1
French 33
Spanish 34
Portuguese 35
Italian 39
German 49
www.gesecurity.net
29