3.4 Remote Display Panel
An installation kit is available for mounting a display panel up to 1 km away from the detector. It
contains:
1 Blanking plate
1 Mounting Box
1 Fixing kit
1. Jumper
Link
2. RS485
3. 24 VDC power
Figure 3-8: Display board and terminal for remotely connecting the Display Panel
Suitable double twisted pair cable for connecting RS485 communications and 24 VDC power can also
be supplied. More information may be found in
Installation Guide for RS485 Equipment
on page 36.
Ensure that the electrical characteristics of the cable connected are appropriate for the distance
between the detector and display module.
When using the double twisted pair cable, use one pair for RS485 communications, the other pair for 24
VDC supply, and ensure that matching signals are connected at each end.
To use the Display Panel remotely, the main unit must also be configured for remote display operation
by following these steps (please see Figure 5-1 for User Function buttons):
1. Press
MENU
2. Use
Parameter
UP
&
DOWN
to reach
SETUP
(Scan and Isolate buttons)
3. Press
ENTER
4. Enter Level 2 Access Code (693) - please refer to
Access Codes
on page 18 for details on the
Access Code
5. Use
Parameter
UP
&
DOWN
to reach
REMPANEL
6. If the display shows REMPANEL 0 then press Value
UP
to get REMPANEL 1
7. Press
ENTER
8. Press
MENU
twice to revert to normal