GE Multilin
F60 Feeder Protection System
7-7
7 COMMANDS AND TARGETS
7.2 TARGETS
7
If none of these apply, then contact the factory.
•
Latched target message
: No.
•
Description of problem
: An Ethernet connection has failed.
•
How often the test is performed
: Monitored every five seconds.
•
What to do
: Check Ethernet connections. Port 1 is the primary port and port 2 is the secondary port.
•
Latched target message
: No.
•
Description of problem
: The SNTP server is not responding.
•
How often the test is performed
: Every 10 to 60 seconds.
•
What to do
: Check SNTP configuration and network connections.
•
Latched target message
: No.
•
Description of problem
: A discrepancy has been detected between the actual and desired state of a latching contact
output of an installed type “4L” module.
•
How often the test is performed
: Upon initiation of a contact output state change.
•
What to do
: Verify the state of the output contact and contact the factory if the problem persists.
•
Latched target message
: No.
•
Description of problem
: A data item in a configurable GOOSE data set is oscillating.
•
How often the test is performed
: Upon scanning of each configurable GOOSE data set.
•
What to do
: The “xxx” text denotes the data item that has been detected as oscillating. Evaluate all logic pertaining to
this item.
•
Latched target message
: No.
•
Description of problem
: A direct device is configured but not connected.
•
How often the test is performed
: Every second.
•
What to do
: Check direct input and output configuration and wiring.
•
Latched target message
: No.
•
Description of problem
: One or more GOOSE devices are not responding.
MAINTENANCE ALERT:
Port ## Failure
MAINTENANCE ALERT:
SNTP Failure
MAINTENANCE ALERT:
4L Discrepancy
MAINTENANCE ALERT:
GGIO Ind xxx oscill
DIRECT I/O FAILURE:
COMM Path Incomplete
REMOTE DEVICE FAIL:
COMM Path Incomplete
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...