5-12
••••
Chapter 5 Diagnostic Interface-Keypad
GEH-6632 EX2100 User’s Guide
2.
Press
Enter
to make a backup copy of the parameters or
Escape
to cancel.
Ø
To restore a parameter from backup
1.
Stop the exciter. (This function cannot be executed with the exciter running.)
2.
From the Main Menu, select Parameter Backup Functions then select Restore
Parameters from Backup.
Press to restore Parameters from Backup
-- WARNING --
The active parameter values will be
replaced, and can not be recovered.
Press ENTER to continue.
ESC cancels.
3.
Press
Enter
to restore the backup parameters or
Escape
to cancel.
Restoring parameters from a backup file overwrites the
currently active parameter values, which cannot then be
restored.
Ø
To compare the active parameter set to the backup parameter set
1.
From the Main Menu, select
Parameter Backup Functions
then select
Compare Current Parameters to Backup
.
BACKUP DIFFERENCES
<More
↑
>
VHiTripLev
= 1.3
Backup value
= 1.2
AFFL
= 112.0
Backup value
= 100.0
VFFL
= 110.0
Backup value
= 100.0
<More
↓
>
2.
Use the
Up
and
Down Arrow
buttons to scroll through the list of backup
differences.
3.
Press
Escape
to return to the previous menu.
Summary of Contents for EX2100
Page 1: ...g GE Industrial Systems GEH 6632 EX2100 Excitation Control User s Guide ...
Page 2: ......
Page 12: ...iv Contents GEH 6632 EX2100 User s Guide Notes ...
Page 44: ...2 24 Chapter 2 Functional Description GEH 6632 EX2100 User s Guide Notes ...
Page 56: ...3 12 Chapter 3 Printed Wiring Boards Overview GEH 6632 EX2100 User s Guide Notes ...
Page 92: ...5 16 Chapter 5 Diagnostic Interface Keypad GEH 6632 EX2100 User s Guide Notes ...
Page 98: ...A 6 Appendix A Warranty and Renewal Parts GEH 6632 EX2100 User s Guide Notes ...
Page 102: ...B 4 Appendix B Ratings and Specifications GEH 6632 EX2100 User s Guide Notes ...
Page 112: ...x Glossary of Terms GEH 6632 EX2100 User s Guide Notes ...
Page 117: ......
Page 118: ... QGXVWULDO 6 VWHPV HQHUDO OHFWULF RPSDQ 5RDQRNH OYG ZZZ LQGXVWULDO FRP 6DOHP 9 86 ...